ENGLISH
ATA Energy Storage System MM
41
User’s manual
12.7
Output Lines and Load Connection
Connect the Output LINE phase of each ATA unit to the respective Output Phase (L1, L2, L3) of the Three Phases
Output Line.
Connect the Output NEUTRAL phase of each ATA and the NEUTRAL of AC Three Phases Output the NEUTRAL power bar.
Connect the EARTH of each ATA unit to the EARTH bar. For safety we recommend to install a protection device (fuse)
on the Output LINE phase of each ATA unit. Refer to the diagram below.
ATTENTION: only the Output LINE connection of each ATA are to be placed under a protection
system. You can not install the security systems on the Output NEUTRAL connection of each ATA.
The Output NEUTRAL lines are placed in common on the NEUTRAL connecting bar.
ATTENTION: be sure that the length of all the power cables is as similar as possible for each
ATA, so as to ensure a right distribution of the absorbed current.
The following table shows the recommended size for wires.
ATA MODEL
MAX CURRENT PROTECTION
(fuse)
WIRE SIZE
TIGHTENING TORQUE
4.0
40 A
10 AWG
1.4 ~ 1.6Nm
5.0
50 A
8 AWG
1.4 ~1.6Nm