ATA Energy Storage System MM
29
User’s manual
11.7
Output Lines and Load Connection
Connect the Output Line (LINE, NEUTRAL and EARTH) of each ATA unit to the respective connection bar. For safety we
recommend to install a protection device (fuse) on the Output LINE connection of each ATA unit. Refer to the diagram
below.
ATTENTION: only the Output LINE connection of each ATA are to be placed under a protection
system. You can not install the security systems on the Output NEUTRAL connection of each ATA.
The Output NEUTRAL lines are placed in common on the NEUTRAL connecting bar.
ATTENTION: be sure that the length of all the power cables is as similar as possible for each
ATA, so as to ensure a right distribution of the absorbed current.
The following table shows the recommended size for wires.
ATA MODEL
MAX CURRENT PROTECTION
(fuse)
WIRE SIZE
TIGHTENING TORQUE
4.0
40 A
10 AWG
1.4 ~ 1.6Nm
5.0
50 A
8 AWG
1.4 ~1.6Nm
11.8
PhotoVoltaic (PV) Panel Connection
Refer to the "Installation" section for the connections of the system of PV panels.
ATTENTION: each ATA unit must be connected to its own system of panels of PV panels. You can
not use only one system of PV panels in common for all ATA units.