MENU 13 – PROGRAMMABLE OUTPUTS
Default
Range
P13.1.1 Adjustable exit function 1
terminal 4.2-4.0-4.1
mains contactor
look at table
P13.1.2 exit 1 Direct / Reverse
Dir
nor-Rev
P13.2.1 Adjustable exit function 2
terminal 4.3 – 4.4
genset contactor
look at table
P13.2.2 exit 2 Direct / Reverse
Dir
nor-Rev
P13.3.1 Adjustable exit function 3
terminal 5.3 – 5.4 – 5.5
global allarm 1
look at table
P13.3.2 exit 3 Direct / Reverse
Dir
nor-Rev
P13.4.1 Adjustable exit function 4
terminal 6.5
fuel solenoid valve
look at table
P13.4.2 exit 4 Direct / Reverse
Dir
nor-Rev
P13.5.1 Adjustable exit function 5
terminal 6.4
starting
look at table
P13.5.2 exit 5 Direct / Reverse
Dir
nor-Rev
P13.6.1 Adjustable exit function 6
terminal 6.3
Stopping magnet
look at table
P13.6.2 exit 6 Direct / Reverse
Dir
nor-Rev
P13.7.1 Adjustable exit function 7
terminal 6.2
Siren
look at table
P13.7.2 exit 7 Direct / Reverse
Dir
nor-Rev
POSSIBLE FUNCTIONS FOR PROGRAMMABLE OUTPUTS
Function
Display reference
Off
OFF
Mains Contactor
M.Con
Generator Contactor
G.Con
Starting motor
Sta.M
Fuel valve
FUEL
Global Alarm 1
GLb.A
Siren
Sire
Decelerator
dECE
Accelerator
ACCE
Stop magnet
STOP
Glow Plugs
G.Plu
Gas valve
GAS
Choke
CHO
Priming valve
Pri
Dummy load
Du.Lo
Compressed air
C.Air
Mode
ModE
No mains present
No.MA
Engine running
E.run
Engine failure
E.FAI
Low Fuel
L.FUE
Generator ready
G.rdy
Global alarm 2
GLb.2
Global alarm 3
GLb.3
Remote controlled relay 1
rEM.1
Remote controlled relay 2
reM.2
Alarms A01-A35 e UA1-UA4
A01…A35…UA4