MENU 10 - COMMUNICATION PORT
Default
Range
P1001 Serial port address RS232
1
1-99
P1002 Baud-Rate RS232
9600
OFF/1200-38400
P1003 Protocol Rs232
Auto
Auto
Prop. ASCII (P.ASC)
Modbus RTU (M.rtu)
P1004 Parity RS-232
nonE
no (nonE)
pari (EvEn)
dispari (Odd)
P1005 Serial port address RS485
1
1-99
P1006 Baud-Rate RS485
9600
OFF/1200-38400
P1007 Protocol Rs485
Auto
Auto
Prop. ASCII (P.ASC)
Modbus RTU (M.rtu)
P1008 Parity RS-485
nonE
no (nonE)
pari (EvEn)
dispari (Odd)
P1009 modem channel
232
OFF / 232 / 485
P1010 Always in AUT way when communication is OFF
OFF
OFF / ON
MENU 11 – MISCELLANEOUS
Default
Range
P1101 Genset Start/stop on threshold (kVA)
OFF
OFF / ON
P1102 Starting threshold (kVA)
0
0-9999
P1103 Engine start threshold dalay (sec)
0
0-999
P1104 Stopping threshold (kVA)
0
0-9999
P1105 Engine stop threshold delay (sec)
0
0-999
P1106 dummy load
OFF
OFF/ON
P1107 dummy load ON (kVA) threshold
0
0-9999
P1108 load ON (sec) delay
0
0-999
P1109 dummy load OFF (kVA) threshold
0
0-9999
P1110 dummy load OFF (sec) delay
0
0-999
P1111 dummy load ON (min) time of cycle
OFF
OFF/1-600
P1112 OFF (min) time of cycle
OFF
OFF/1-600
P1113 Rent hours (h)
OFF
OFF/1-60000
P1114 Mode select
Normal
Normal/EJP/
EJP-T/SCR
P1115 Start engine delay (EJP)
25min
0-99
P1116 Changeover delay
5min
0-30
P1117 Changeover block
ON
OFF / ON
P1118 AUT and TEST block
OFF
OFF / ON
P1119 Engine start in case of TLR failure
OFF
OFF / ON
P1120 Exit functioning way
OFF
OFF / r / M / M+r / …./ t+a+r+m