2.1.1 - How to programming the time
1) Push RESET + MEAS for 5 seconds at the same time. You can release buttons when display shows the word “Set” and consequently the first
parameter “
01.01
”. The table above shows all parameters of this menu called "UTILITY". The first parameter indicates the
actual year
.
2) Push TEST or MAN button to view the default setting.
Continuing to press TEST it increases the value by pressing MAN it decreases.
If you
don’t press any button, after about 2 seconds the display goes back to show the parameter "01.01".
3) Push TEST
button to move to the next parameter “
01.02
”, when you want to come back to previous parameters press STOP button. The
“01.02” parameter allows to set the
actual month
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value, by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.02".
4) Push TEST
button to move to the next parameter “
01.03
”: this parameter allows to set
the number of actual day in the month
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.03".
5) Push TEST
button to move to the next parameter “
01.04
”: this parameter allows to set the
actual day in the week
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.04".
In case is entering a wrong day, the board automatically corrects the data, because it is synchronizes by year, month and date of the actual day.
6) Push TEST
button to move to the next parameter “
01.05
”: this parameter allows to set the
actual hour
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.05".
7) Push TEST
button to move to the next parameter “
01.06
”: this parameter allows to set the
actual minutes
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.06".
8) Push TEST
button to move to the next parameter “
01.07
”: this parameter allows to set the
actual seconds
.
Push TEST or MAN button to view the default setting. Continuing to push TEST it increases the value by pushing MAN it decreases.
If you don’t
press any button, after about 2 seconds the display goes back to show the parameter "01.07".
The clock time programming is now finished.
Press RESET button to save the statements and exit the menu to come back to normal operating mode.
If the date and clock time are not fixed, the yellow led TEST
, flashes indicating that it is not guaranteed the exact starting of automatic test.
The next parameters “01.08”, “01.09”, “01.10” concerning different functions than the date and the time.
2.1.2 - How to programming the atomatic test
It’s strongly recommended the enabling of the automatic test to prevent problems caused by a long inactivity of the generator.
MENU 09 – TEST AND MAINTENANCE
Default
Range
09.01 Automatic test on
OFF
OFF / ON
09.02 Interval between TESTS (days)
7
1-30
09.03 To enable test on Monday
ON
OFF / ON
09.04 To enable test on Tuesday
ON
OFF / ON
09.05 To enable test on Wednesday
ON
OFF / ON
09.06 To enable test on Thursday
ON
OFF / ON
09.07 To enable test on Friday
ON
OFF / ON
09.08 To enable test on Saturday
ON
OFF / ON
09.09 To enable test on Sunday
ON
OFF / ON
09.10 Hour starting test (h)
12
00-23
09.11 Minutes starting test (min)
00
00-59
09.12 Automatic test duration (min)
OFF
OFF/1-600
09.13 Automatic test with switching load
OFF
OFF / G.con / du.Lo
09.14 Automatic test with remote stop
OFF
OFF/ON
09.15 Maintenance interval (h)
OFF
OFF/1-9999
09.16 TEST way with switching load
OFF
OFF / G.con / du.Lo
MENU 01 – UTILITY’
Default
Range
01.01 Year
2006
2000-2100
01.02 Month
1
1-12
01.03 Day of the month
1
1-31
01.04 Day of the week
1
Mon, Tue, … Sun
01.05 Hour
0
0-23
01.06 Minutes
0
0-59
01.07 Seconds
0
0-59
01.08 Clock setting at power-up
ON
OFF/ON
01.09 Return to main measure (sec)
60
OFF/5-999
01.10 Alarm messages on display
On
OFF / On