TFA1-298
35
A
P
FIRE ZONE - BEHAVIOR AFTER PREALARM
The zone is in stand-by state
A device in prealarm state
switches the zone
to prealarm
Double-knock
zone prealarm
timeout
Behavior
after prealarm
On the basis of the setting, the zone remains
in prelarm or switches to alarm
DOUBLE-KNOCK FIRE ZONE - ALARM TRIGGERING FROM A MANUAL CALL POINT
The zone is in stand-by state
An alarm from a manual call point in alarm state (pressed)
immediately triggers the alarm noti
fi
cations
Yes
No
Prealarm
timeout
Prealarm
timeout
expired
?
Prealarm
state stops
Prealarm
state continues
Zone switches
to alarm
None
Alarm
Behavior
after
prealarm
Alarm
No alarm
Prealarm
Prealarm
No alarm
No alarm
Alarm