![Tecnoalarm Tecnofire TF-A1-298-DE Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/tecnoalarm/tecnofire-tf-a1-298-de/tecnofire-tf-a1-298-de_installation-manual_1071798023.webp)
TFA1-298
23
OK
OK
ESC
Each event in the list is identi
fi
ed by the event type icon, date, time,
alarm type and source.
The last event of the list is indicated by the words
End of list
.
N.B.
Since the control panel controls the zones, the failures and
the alarms of the individual detectors and modules are not added
up in the count, but they are considered integral to the individual
zones. Accordingly, for the events related to a zone, to the left of the
cursor a number is displayed, indicating how many detectors and/or
modules of the zone are affected by the event.
Selecting the event with the cursor and pressing the
OK
key the
view of the zone is expanded showing the detail of the devices.
With the pointer over an event, pressing the acknowledgment key,
the speaker issues the description of the event.
In the case of an alarm and if the zone has an associated alarm
plan, by pressing again the acknowledgment key, a pop-up window
appears that displays the text of the alarm plan.
The alarm plan remains visible for 10 seconds.
To exit the alarm plan display, press the
ESC
key.
Consultation of the event storage folders
To view and browse the contents of the folders, use the navigation
keys.
If you select a folder whose counter shows a number other than 0000,
as in the example the folder
Preal.
, the relative events are displayed.
Select the next folder
Select the previous folder
Scroll the event list down
Scroll the event list up
Expand the display of the event pointed by the cursor
Exit the expanded view
Total zones in alarm: 1
16/02/2019
16/02/2019
16/02/2019
08:00:00
08:00:00
08:00:00
Access level 1
Access level 1
Access level 1
Level 2
Level 3
Level 4
Test
0000
Alarm
0001
Preal.
0000
Tech. Al.
0000
Failure
0000
Excl.
0000
08/03/2018 08:00:00
Alarm
(2)
Control panel 1
Hotel Aurora
Zone 1
Administration
- - - End of list - - -
Total zones in alarm: 1
First:
Administration
[Zone 1 Ctrl. 1]
Last:
Administration
[Zone 1 Ctrl. 1]
Level 2
Level 3
Level 4
Test
0000
Alarm
0001
Preal.
0000
Tech. Al.
0000
Failure
0000
Excl.
0000
08/03/2018 08:00:00
Allarme
(2 di 2)
Control panel 1
Hotel Aurora
Zone 1
Administration
08/03/2018 08:00:00
Detector alarm
Detector 10 Line 1
Marco's of
fi
ce
optical alarm
Total zones in alarm: 1
Level 2
Level 3
Level 4
Fire alarm plan
Evacuate the marketing dept., 1st
fl
oor, following the
escape route, south side.
Reach assembly point 2.
16/02/2019
08:00:00
Access level 1
Level 2
Level 3
Level 4
Test
0000
Alarm
0000
Preal.
0001
Tech. Al.
0000
Failure
0000
Excl.
0000
First:
Administration
[Zone 1 Ctrl. 1]
Last:
Administration
[Zone 1 Ctrl. 1]
Fire control panel
Release: 2.0.00 ENG
No alarm active
EVENT STORAGE FOLDERS
Name
Icon
Description
Name
Icon
Description
Alarm
0000
The folder logs and counts all
fi
re alarms
divided by zone
Failure
0000
The folder logs and counts all zone and system failures
Preal.
0000
The folder logs and counts all
fi
re prealarms
divided by zone
Excl.
0000
The folder logs all excluded items (i.e. put out of service)
Tech.Al.
0000
The folder logs and counts all technical
alarms and prealarms divided by zone
Test
0000
The folder logs all alarms recorded by the devices
under test
N.B.
The folders can contain up to a maximum of 8192 events. The folders are cleared and the counters are reset each time the control panel is reset.
The events remain stored in the event buffer of the control panel.
Содержание Tecnofire TF-A1-298-DE
Страница 2: ...TFA1 298 2 ...
Страница 4: ...TFA1 298 4 ...
Страница 10: ...TFA1 298 10 ...
Страница 14: ...TFA1 298 14 ...
Страница 28: ...TFA1 298 28 ...
Страница 32: ...TFA1 298 32 ...
Страница 40: ...TFA1 298 40 ...
Страница 46: ...TFA1 298 46 ...
Страница 55: ...TFA1 298 55 NOTES ...