6 - FAILURE NOTIFICATIONS
The control panel manages two types of failures: system failures and general failures. System failures are a special category of
failures that refer to the standard EN 54-2. General failures group all the other types of failures.
SYSTEM FAILURES
Failure event
Description
Automatic
acknowledgment
Reset by watchdog
The control panel has detected a reset signal that has been generated by the
watchdog circuit.
No
KEY jumper inserted with an access level
lower than level 4
The KEY jumper has been inserted while the control panel was not at access level 4.
Yes
Failure of control panel buffer
The RAM and FLASH memories of the control panel are automatically checked
every 30 minutes. The detection of any malfunction during the test triggers the
failure noti
fi
cation.
No
N.B.
With the
Automatic system failure acknowledgment
option enabled, the noti
fi
cation is stopped when the failure state ends.
With the
Automatic system failure acknowledgment
option disabled, the noti
fi
cation cannot be automatically stopped but continues even when the failure state is over.
In this case, to stop the noti
fi
cation, it is necessary to reset the control panel.
GENERAL FAILURES
Failure event
Automatic
acknowledgment
Failure event
Automatic
acknowledgment
Communication missing among control panels or repeaters
Yes
Open loop
No
Low battery
Yes
Short-circuited loop
No
Battery failure
Yes
Overvoltage
Yes
Power failure
Yes
Siren termination resistor missing
Yes
Inconsistent programming
No
Ethernet interface failure
No
Earth leakage
Yes
Ethernet connection missing
Yes
Power supply failure
Yes
Communication missing (channel)
Yes
Open RS485 loop
Yes
No answer (channel)
Yes
N.B.
With the
Automatic system failure acknowledgment
option enabled, the noti
fi
cation is stopped when the failure state ends.
With the
Automatic system failure acknowledgment
option disabled, the noti
fi
cation cannot be automatically stopped but continues even when the failure state is over.
In this case, to stop the noti
fi
cation, it is necessary to reset the control panel.
System failure
System failure
16/02/2019
08:00:00
Access level 1
Control panel 1
Hotel Aurora
KEY JP inserted
16/02/2019 08:00:00
16/02/2019
08:00:00
Access level 1
Failure
Failure
Control panel 1
Aurora Hotel
Console 1
Communication missing
16/02/2019 08:00:00
Содержание Tecnofire TF-A1-298-DE
Страница 2: ...TFA1 298 2 ...
Страница 4: ...TFA1 298 4 ...
Страница 10: ...TFA1 298 10 ...
Страница 14: ...TFA1 298 14 ...
Страница 28: ...TFA1 298 28 ...
Страница 32: ...TFA1 298 32 ...
Страница 40: ...TFA1 298 40 ...
Страница 46: ...TFA1 298 46 ...
Страница 55: ...TFA1 298 55 NOTES ...