TFA1-298
24
The operating states of the control panel are noti
fi
ed optically and acoustically and according to the level of priority (see below table).
5-6 - Noti
fi
cation of operating states
Priority level
Operating state
Priority level
Operating state
1
Fire alarm
4
Technical prealarm
2
Fire prealarm
5
Failure
3
Technical alarm
6
Stand-by
STAND-BY STATE - NO ALARM ACTIVE
Normal operating state, no failure active, all detectors in stand-by.
Signaling
The display shows the normal operating state
MAINS PWR OK
LED on
MONITORED
LED on or off depending on the selected state
TX CARRIED OUT
LED off
All the other LED are off
No siren is active
No output is active
16/02/2019
08:00:00
Access level 1
Level 2
Level 3
Level 4
Release: 2.0.00 ENG
Control panel working
Fire control panel
FIRE PRELARM STATE
A double-knock zone in alarm or, with active monitored system mode, a single-knock zone in alarm, or a detector in prealarm state.
Signaling before
acknowledgment
The speaker issues the audible prealarm signal
The
PREALARM
LED
fl
ashes
The output programmed for prealarm is triggered
The display shows the prealarm state
Signaling after the
fi
rst
acknowledgment
The speaker is muted
The
PREALARM
LED turns on steadily
The display shows the list of active prealarms
Signaling after the second
acknowledgment
The speaker issues the list of zones in prealarm state
16/02/2019
08:00:00
Access level 1
Prealarm
Control panel 1
Zone 1
16/02/2019 08:20:20
FIRE ALARM STATE
A single-knock zone in alarm, or multiple detectors of a double-knock zone in alarm or, with active monitored system mode, end of double-knock zone prealarm timeout.
Signaling before
acknowledgment
The speaker issues the audible alarm signal
The
ALARM
LED
fl
ashes
The alarm relay is activated
The display shows the alarm state
Signaling after the
fi
rst
acknowledgment
The speaker is muted
The
ALARM
LED turns on steadily
The display shows the list of active alarms
Signaling after the second
acknowledgment
The speaker issues the list of zones in alarm state
In case of a zone alarm, the display shows the associated
alarm plan
16/02/2019
08:00:00
Access level 1
Alarm
Control panel 1
Hotel Aurora
Administration
Zone 1
16/02/2019
08:00:00
Содержание Tecnofire TF-A1-298-DE
Страница 2: ...TFA1 298 2 ...
Страница 4: ...TFA1 298 4 ...
Страница 10: ...TFA1 298 10 ...
Страница 14: ...TFA1 298 14 ...
Страница 28: ...TFA1 298 28 ...
Страница 32: ...TFA1 298 32 ...
Страница 40: ...TFA1 298 40 ...
Страница 46: ...TFA1 298 46 ...
Страница 55: ...TFA1 298 55 NOTES ...