TFA1-298
31
TABLE 4 - BATTERY CHARGER FAILURE
The test is performed every second. The failure is noti
fi
ed when the test detects for more than 5 minutes the presence of mains power, but not the battery charging current.
Test frequency
1 second
Delay of failure noti
fi
cation
5 minutes
Signaling on occurence of failure
The
PWR SPLY FAILURE
LED starts
fl
ashing
Signaling on noti
fi
cation of failure
The control panel display shows
FAIL. PWR SUP./BATT. CHARGER
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
PWR SPLY FAILURE
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
The failure noti
fi
cations are reset after detecting the battery charging current for 5 minutes.
TABLE 5 - OVERVOLTAGE
The test is performed every second. The failure is noti
fi
ed when the test detects, for more than 60 seconds, that the power supply voltage required by the external
devices exceeds 30V.
Test frequency
1 second
Delay of failure noti
fi
cation
60 seconds
Signaling on occurence of failure
The
PWR SPLY FAILURE
LED starts
fl
ashing
Signaling on noti
fi
cation of failure
The control panel display shows
OVERVOLTAGE FAILURE
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
PWR SPLY FAILURE
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
The failure noti
fi
cations are reset after detecting, for 60 seconds, that the power supply voltage required by the
external devices has returned to the rated value of 30V.
TABLE 6 - LOW BATTERY
The test is performed only in case of power failure, with an interval of 1 second. The failure is noti
fi
ed when the test detects for more than 15 minutes a battery
voltage below 21.6V.
Test frequency
1 second
Delay of failure noti
fi
cation
15 minutes
Signaling on occurence of failure
The
BATTERY
LED starts
fl
ashing
Signaling on noti
fi
cation of failure
The control panel display shows
LOW BATTERY
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
BATTERY
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Reset of faillure noti
fi
cations
Failure noti
fi
cations are reset after detecting, for at least 30 seconds, a battery voltage above 22.8V.
TABLE 7 - DISCHARGED BATTERY
The test is performed only in case of power failure. If the test detects for 15 minutes a battery voltage below 18V, the power supply section disconnects the batteries
and shuts down.
Signaling 10 seconds before
power supply shut down
The control panel display shows
BATTERY FAILURE
The failure noti
fi
cation is stored in the failure folder and the relative counter is incremented
The
BATTERY
LED turns on steadily
The
GENERAL FAILURE
LED starts
fl
ashing
The failure relay is activated
Содержание Tecnofire TF-A1-298-DE
Страница 2: ...TFA1 298 2 ...
Страница 4: ...TFA1 298 4 ...
Страница 10: ...TFA1 298 10 ...
Страница 14: ...TFA1 298 14 ...
Страница 28: ...TFA1 298 28 ...
Страница 32: ...TFA1 298 32 ...
Страница 40: ...TFA1 298 40 ...
Страница 46: ...TFA1 298 46 ...
Страница 55: ...TFA1 298 55 NOTES ...