TD20 Series VFD
Function Parameters
-54-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
g AO2 output
to the upper
limit
Setting range of P06.24: P06.22
–100.0%
Setting range of P06.25: 0.00V
–10.00V
Setting range of P06.26: 0.000s
–10.000s
P06.26
AO2 output
filter time
0.000s
○
P07 Group Human-Machine Interface
P07.00
User's
password
0
–65535
The password protection will be valid when setting any
non-zero number.
00000: Clear the previous user's password, and make
the password protection invalid.
After the user's password becomes valid, if the
password is incorrect, users cannot enter the parameter
menu. Only correct password can make the user check
or modify the parameters. Please remember all users'
passwords.
Retreat editing state of the function codes and the
password protection will become valid in 1 minute. If the
password is available, press PRG/ESC to enter into the
editing state of the function codes, and then "0.0.0.0.0"
will be displayed. Unless input right password, the
operator can not enter into it.
Note:
Restoring to the default value can clear the
password, please use it with caution.
0
○
P07.01
Parameter
copy
0: No operation
1: Upload the local function parameter to the keypad
2: Download the keypad function parameter to local
address (including the motor parameters)
3: Download the keypad function parameter to local
address (excluding the motor parameter of P02 and P12
group)
4: Download the keypad function parameters to local
address (only for the motor parameter of P02 and P12
group)
Note
: After finish 1
–4, the parameter will restore to 0
and the uploading and downloading does not include
P29.
0
◎
P07.02
Key
function
Ones: QUICK/JOG key function
0: Null
1
◎