TD20 Series VFD
Communication Protocol
-103-
Low bit of data content
ABH
CRC CHK low bit
ADH
CRC CHK high bit
14H
END
T1-T2-T3-T4
7.3.4 Command code: 10H, continuous writing
Command code 10H means that if the master writes data to the VFD, the data number depends on the
"data number" in the command code. The Max. continuous reading number is 16.
For example, write 5000 (1388H) to 0004H of the VFD whose slave address is 02H and 50 (0032H) to
0005H, the frame structure is as below:
The RTU request command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
High bit of write data
00H
Low bit of write data
04H
High bit of data number
00H
Low bit of data number
02H
Byte number
04H
High bit of data 0004H
13H
Low bit of data 0004H
88H
High bit of data 0005H
00H
Low bit of data 0005H
32H
Low bit of CRC
C5H
High bit of CRC
6EH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
The RTU response command is:
START
T1-T2-T3-T4 (transmission time of 3.5 bytes)
ADDR
02H
CMD
10H
MSB of write data
00H
LSB of write data
04H
MSB of data number
00H
LSB of data number
02H
LSB of CRC
C5H
MSB of CRC
6EH
END
T1-T2-T3-T4 (transmission time of 3.5 bytes)
7.3.5 The definition of data address
The address definition of the communication data in this part is to control the running of the VFD and get
Содержание TD20 Series