8
boiler req.
M with 0-10V-
outp. possible
Diagram 16: Automatic boiler, cylinder, heating circuit (without mixer),
burner demand
If no room sensor is used, the room influence
RI
in menu
MIXER
must be set to zero and the
sensor
S1
in the
SENSOR
menu set to
FIXED VALUE (e.g. 20°C)
.
A3= Burner
demand
Required settings:
Basic control level
Time
Operating mode (preferably
AUTO
)
Set room temperature for lowering mode
RTL
Set room temperature for normal operation
RTN
Time program
for normal operation and burner demand (time program 1-
4), hot water (time program 5)
Parameter menu
Program number
PR
min1
... boiler
S4
A1
,
A2 diff1
… boiler
S4
– cylinder
S5
A2
min2
… boiler
S4
A3
diff2
… boiler
S4
– NP
A3
max1
… cylinder
S5
A2, A3 max2
… boiler
S4
A3
Heating curve
TEMP
or
R RISE
Flow maximum and minimum temperature (
PRE
max,
PRE
min)
Parameter frost protection mode (
OTF
,
RTF
)
Menu Men
MIXER
(Room influence etc.) and
PUMP
(Switch off conditions)
A1 off
A2 off
S4 < min1 S4 < min1
diff1
A1 on
A2
on
Switch-off condition S5 > max1
PUMP
(if heating active)
A1 off
A2 off
Burner demand
A3
S4 < max2
and
S5 < max1
and
Time program 5
or
Heating active
and
S4 < min2
or
Heating active
and
S4
<
NP
+
diff2
(NP = set flow temperature)
S3 for p8