Heating pump menu PUMP
In this menu the
switch-off conditions for the heating pump
and the mixer behaviour with
switched-off pump are specified.
RT OFF
Switch off when set room temperature has been reached.
PN
<
PM
Switch off when the calculated set flow temperature falls below the minimum flow
temperature.
OTNOFF
Switch off when the average outdoor temperature exceeds a specified value
in normal operation.
OTLOF
F Switch off when the average outdoor temperature exceeds a specified value
in lowering mode.
M BEH
Mixer behaviour when switching off the heating pump.
Switch-off when the set room temperature is reached
ON/OFF
Switch-off condition activate/deactivate. (fs = OFF)
Base temperature is the set room temperature for normal or lowering mode in the
basic control level (
RTN
/
RTL
).
HYS
Switching hysteresis of the base temperature. (fs = 0.5 K) Setting range: 0 to 25 K
The switching hysteresis has an upward effect.
Example
: with a set room temperature of
20°C and a hysteresis of 0.5K the pump is switched off at 20.5°C as the temperature in-
creases and switched on again at 20.0°C as the temperature falls.
ON/OFF Hysteresis