33
TIMEPx
Selection of time programs 1 to 5 and entry with the lower arrow key
MO
By setting ON and OFF for each day it is determined whether on this day
until
SU
the time program is activated.
TIME W
Entry with the lower arrow key after which the switch-on and switch-off times for the
time window 1 can be entered.
NV
Set room temperature value for time window 1
NV -- = no set value for the time window;
RTN
is used.
The time windows 2 and 3 can be set in the same way; the appropriate digits are
shown in the lower line of the display.
RAT
Rate time in minutes. Adjusts the switch-on point fixed in the time window according
to outdoor temperature. This entry refers to an outdoor temperature of -10°C and is
0 at plus 20°C. For example, if the rate time is 30 minutes and the outdoor tempera-
ture is 0°C, the system will switch on 20 minutes earlier under normal operation.
Ad-
justment range 0-255 min
Date setting DATE
M05 17
Setting of month and day. Change between month and day using the downward
arrow key. Select with the lateral arrow key and confirm with upward arrow.
Y 2012
Setting the year
AUTO
Automatic changeover from normal to summertime. With the selection
NORMAL
fixed setting of the normal time is made.
Time window
Switch-on time 1
Switch-off time 1
Set value room
temperature
time window 1
Switch on time 2
(not yet pro-
grammed)
Date
M
onth
05
Day
17
Year
Changeover
Summertime/normal
time