29
NP
Calculated set flow temperature. The set flow value is calculated on the basis
of the heating curve, the outdoor temperature recorded and where appropriate
taking the influence of a room sensor into account.
The heating circuit controller attempts to reach this temperature at the flow
sensor TP through mixer OPEN/CLOSE.
T4-6
Allocation of the sensor inputs S4 to S6 is dependent on the program. T4, T5
and T6 therefore indicate the actual measured temperature as long as the in-
puts have been allocated.
NORM Stat
Status display of the heating circuit controller with the possible displays:
NORM
– normal operation,
LOW
– lowering mode,
STB
– standby mode
MALF
– malfunction,
FRO
– frost protection mode,
STAT
– display for pro-
grams 64 – 66,
COOL
– Cooling operation for programs 128 – 131.
Additionally the lower display area contains the symbol-based Status display.
PARTY
Operating mode of the heating circuit controller. Capable of being set with the
arrow keys are:
AUTO
– automatic operation
NORMAL
– permanent control of the room temperature set for normal opera-
tion
LOWER
– permanent control of the room temperature set for lowering mode
PARTY
– heating is carried out up to a pre-set time P XX.XX
LEAVE
– from the current date up to the date MXX XX 24:00 the controller
operates only in lowering mode
HOLID(AY)
– public holiday mode; from the current day the controller takes
over the Saturday heating times until the date MXX XX and for this date the
Sunday heating times
STB
(Standby) – the control function is switched off; the frost protection func-
tion is activated
For the modes of operation
PARTY
,
LEAVE
and
HOLID
the controller switch-
es back to automatic operation after the time indicated has expired.
P 02.30
Additional parameter for mode: party, holiday or leave. Here the time for party
mode (in example up to 2:30 AM) or the date set for leave and holiday modes.
RTL
Required room temperature for
lowering mode
. Set value for the room tem-
perature outside the time window. If no time program is setup, then RTL is
used as the set value. (fs = 15°C), setting range 0 to 30°C
RTN
Required room temperature in
normal operation
. This value is used as the
set value for the room if the time program does not specify a different one (fs =
22°C), setting range 0 to 30°C.
TIMEPR
Entry to the time programs menu
ENTER Par
Entry to the parameters menu
ENTER Men
Entry to the main menu