Mixer menu MIXER
Outdoor tempera-
ture control
Room influence
Increase in
switch-on power
Fixed value
control
Mixer run time
Determination of
average
outdoor temp.
Current
OT
average
OT CON
Type of control: Outdoor temperature. Calculation of set flow temperature from the
outdoor temperature and a pre-determined correlation (Temperature or rate of
rise, setting in parameter menu
Par
).
FV CON
Type of control: Fixed value control. The flow is controlled to the specified temper-
ature of +10°C in lowering mode and to that of -20°C in heating mode
(
setting in
parameter menu Par).
Important instruction for fixed value control
: As room influence is still active,
then if a room sensor is being used, the room influence
RI
must be set to zero.
RI
Room influence. The respective room temperature is taken into consideration for
calculating of the flow. (fs = 50%) Setting range: 0 – 90%
ISO
Increase in switch-on power in % relative to a lowering time of 10 hours. The pre-
vious lowering period leads to an excessive increase (receding over time) of the
flow temperature to shorten the dwell time.(fs = 0%) Setting range: 0 – 9%
RT
Total mixer run time in minutes. (fs = 3.0)
Setting range: 0 to 30 min
AVT
Averaging time of the outdoor temperature for the calculation of the set flow in
minutes. Compensation of the fluctuating outdoor temperatures for the calculating
the flow temperature. (fs = 10) Setting range: 0 to 255 min
AV
Actual average value for the outdoor temperature.