12
1.3.4 Replacing UPS Internal Batteries
Follow the steps and Charts as below to replace batteries:
1.
Take off the LCD box, and remove the screws.
2.
Slide and Pull the front panel leftward and then take it off.
3.
Disconnect the cable from the UPS and battery pack.
4.
Remove the right inner battery bracket.
5.
Pull the battery pack out onto flat area.
6.
Install new battery pack into UPS.
7.
Screw up the battery bracket and reconnect the battery cable A and B
8.
Re-install the front panel back to UPS.
Note:
If you are not qualified service personnel to replace the battery, do not
attempt to open the battery cabin. Please call local dealer or distributor
immediately.
5
7
13
1.3.5 Testing New Batteries
For a battery test, please check:
l
The batteries must be fully charged.
l
The UPS must be in Normal mode with no active alarms.
l
Don’t take on/off the load.
To test batteries:
1. Connect the UPS to utility power for at least 48 hours to charge the
batteries.
2. Press and hold the
“I”
button 1 second to start the battery test on line mode
or HE mode. The status display string shows “TEST”
1.3.6 Recycling the Used Battery:
To recycle properly the used battery, please do not discard the UPS, battery
pack and batteries into the trash bin. Please follow your local laws and
regulations; you may contact your local recycling waste management center
for further information to dispose properly of the used UPS, battery pack, and
batteries.
1.4 Transport
★
Please transport the UPS only in the original packaging (to protect against
shock and impact).
1.5 Storage
★
The UPS must be stockpiled in the room where it is ventilated and dry.
Warning:
l
Never dispose the batteries in a fire. It may explode.
l
Do not open or mutilate the batteries. Released electrolyte is harmful
to the skins and eyes. It may be toxic. A battery can present a risk of
electrical shock and high short circuit current.