9. Maintenance
9.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life
(3~5 years at 25°C ambient temperature) has been exceeded, the batteries
must be replaced. In this case please contact your dealer.
9.2 Storage
If the batteries are stored in temperate climatic zones, they should be charged
every three months for 1~2 hours. You should shorten the charging intervals to
two months at locations subject to high temperatures.
9.3 Battery Replace
If the battery service life has been exceeded, the batteries must be replaced.
Battery replacement should be performed only by qualified personnel.
It recommends to shut off the UPS completely before the replacement. If there
is a battery breaker then turn it off first. Disconnect the battery cable carefully
and make sure no any exposed wires can be touched. Reconnect the new
batteries to the UPS by following section 5.8. Then turn on the battery breaker
and start the UPS.
If it needs to replace the batteries while the UPS is running, make sure the
UPS would not shut down during the replacement. If there is a battery breaker
then turn it off first. Disconnect the battery cable carefully and make sure no
any exposed wires can be touched. Reconnect the new batteries to the UPS
by following section 5.8. Then turn on the battery breaker and press the ON
switch to make the UPS do the battery test, check whether the battery
information is normal.
33
10. Technical Data
10.1 Electrical specifications
INPUT
Model No.
1K & 1K-KS
2K & 2K-KS
3K & 3K-KS
Phase
1
Frequency
(45~55)/(54~66) Hz
Max Current(A)
7.5
13.5
20
OUTPUT
Model No.
1K& 1K-KS
2K& 2K-KS
3K & 3K-KS
Power rating
1KVA/0.9KW
2KVA/1.8KW
3KVA/2.7KW
Voltage
208/220/230/240
×
(
1
士
1%
)
VAC
Frequency
50/60
(
±
0.2
)
Hz (Battery mode)
Wave form
sinusoidal
BATTERIES
Model No.
1K
2K
3K
Number and type
3
×
12V 7Ah
4
×
12V 9Ah
6
×
12V 9Ah
10.2 Operating Environment
Ambient Temperature
0 oC to 40 oC
Operating humidity
< 95%
Altitude
< 1000m
Storage temperature
0 oC to 45 oC
10.3 Typical backup time (Typical values at 25°C in minutes:)
Model No.
100 % Load
50 % Load
1K
5
15
2K
3
10
3K
3
10