9. Maintenance 

9.1 Operation 

The UPS system contains no user-serviceable parts. If the battery service life 
(3~5  years  at  25°C  ambient  temperature)  has  been  exceeded,  the  batteries 
must be replaced. In this case please contact your dealer. 

9.2 Storage 

If the batteries are stored in temperate climatic zones, they should be charged 
every three months for 1~2 hours. You should shorten the charging intervals to 
two months at locations subject to high temperatures. 

9.3 Battery Replace 

If the battery service life has been exceeded, the batteries must be replaced. 

Battery replacement should be performed only by qualified personnel. 

It recommends to shut off the UPS completely before the replacement. If there 
is a battery breaker then turn it off first. Disconnect the battery cable carefully 
and  make  sure  no  any  exposed  wires  can  be  touched.  Reconnect  the  new 
batteries to the UPS by following section 5.8. Then turn on the battery breaker 
and start the UPS. 
If  it  needs  to  replace  the  batteries  while  the  UPS  is  running,  make  sure  the 
UPS would not shut down during the replacement. If there is a battery breaker 
then  turn  it  off first. Disconnect  the battery  cable  carefully  and make sure  no 
any exposed wires can be touched. Reconnect the new batteries to the UPS 
by  following  section  5.8.  Then  turn  on  the  battery  breaker  and  press  the  ON 
switch  to  make  the  UPS  do  the  battery  test,  check  whether  the  battery 
information is normal. 

 

 
 
 
 
 
 

 
 
 

 

33 

10. Technical Data 

10.1 Electrical specifications 

INPUT 

Model No.

 

1K & 1K-KS

 

2K & 2K-KS

 

3K & 3K-KS

 

Phase

 

Frequency

 

(45~55)/(54~66) Hz

 

Max Current(A)

 

7.5 

13.5 

20 

OUTPUT 

Model No. 

1K& 1K-KS

 

2K& 2K-KS

 

3K & 3K-KS

 

Power rating 

1KVA/0.9KW 

2KVA/1.8KW 

3KVA/2.7KW 

Voltage 

208/220/230/240

×

1

1%

VAC 

Frequency 

50/60

±

0.2

Hz (Battery mode) 

Wave form 

sinusoidal 

BATTERIES 

Model No. 

1K 

2K 

3K 

Number and type 

3

×

12V 7Ah 

4

×

12V 9Ah 

6

×

12V 9Ah 

 

10.2 Operating Environment 

Ambient Temperature 

0 oC to 40 oC 

Operating humidity 

< 95% 

Altitude 

< 1000m 

Storage temperature 

0 oC to 45 oC 

10.3 Typical backup time (Typical values at 25°C in minutes:) 

Model No. 

100 % Load 

50 % Load 

1K 

15 

2K 

10 

3K 

10 

Содержание AP160N Series 1000VA

Страница 1: ...iption 17 5 Connection and Operation 19 5 1 Inspection 19 5 2 Connection 19 5 3 Battery charge 21 5 4 Turn on the UPS 21 5 5 Test function 21 5 6 Turn off the UPS 22 5 7 Audible alarm mute function 22...

Страница 2: ...ssure to connect with the earth reliably Assure external battery source must be earthed Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet shockproof socket...

Страница 3: ...the end of the tower 2 Place down the UPS into two stands carefully 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel 5 l Rack mount...

Страница 4: ...battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reas...

Страница 5: ...the gate and then reassemble front panel B C A D E 9 Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the num...

Страница 6: ...alified maintenance personnel 1 3 1 UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the s...

Страница 7: ...ake on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the I button 1 second to start the battery test on line mode or...

Страница 8: ...D IEC EN 61000 4 2 Level 3 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 1...

Страница 9: ...KS Extended backup time 17 4 Panel Description The Display Panel Switch Function ON Button Turn on UPS system By pressing the ON Button I the UPS system is turned on Deactivate acoustic alarm By press...

Страница 10: ...orm the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to pre...

Страница 11: ...ed 5 4 Turn on the UPS 1 With utility power connecting Press I button continuously for more than 1 second to turn on the UPS the UPS will get into the inverter mode the LCD screen will indicate the st...

Страница 12: ...will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connecting the battery pack 3 The battery connection procedure is very important Any i...

Страница 13: ...nominal power capacity 25 Note Please follow the following steps to connect the generator l Activate the generator and wait until the operation is stable before supplying power of the generator to th...

Страница 14: ...hile the utility power is in normal range so the high efficiency could be gained in the ECO mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied cont...

Страница 15: ...for more than 10 seconds the setting mode exit automatically The output frequency string OPF Bypass status string bYPA operating mode string MOdE Battery string bSTR Load segment string LS1 and LS2 wo...

Страница 16: ...battery voltage is normal and the mains is normal charge automatically again Battery low Battery voltage is low When audible alarm sounding every second battery is almost empty 31 Charge fail The cha...

Страница 17: ...d start the UPS If it needs to replace the batteries while the UPS is running make sure the UPS would not shut down during the replacement If there is a battery breaker then turn it off first Disconne...

Страница 18: ...a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable...

Страница 19: ...er WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems...

Страница 20: ...1 AC Output 2 EPO Dry input Communication Port 3 USB Port 4 AC Input 5 Dry out 6 SNMP slot 7 RS232 8 Modem Network Surge Protection 9 Earth Line connection 39 1 1 3K Standard model rear panel 3K KS mo...

Отзывы: