28 

7. Setting by LCD Module

 

The output voltage, frequency, Bypass status and operating mode in No output 
mode or Bypass mode, Two Load segments in output mode, Battery string in 
all mode could be set directly through LCD module. The output voltage could 
be  set to  208V, 220V, 230V  and  240V.  The  output frequency  could be  set to 
50Hz  and  60Hz.  The  bypass  state  could  be  set  to  enable  and  disable.  The 
operating mode of UPS could be set between the Line mode, ECO mode and 
Converter mode. Battery string could be set to one to night groups. Two Load 
segments could be set to on and off. 

In bypass or no output mode, pressing the “Enter” button on the LCD panel for 
more than one second to enter setting mode. The LCD display is shown in the 
following diagram. The string “OPV” indicates that the current setting is output 
voltage. “230Vac” indicates the current default output voltage is 230Vac. if you 
want to set output voltage, press the “Enter” button for more than one second, 
a flickering string “208” would be shown, if the “Enter” button is pressed again, 
the  string  “208”  turn  to  flickerless,  the  output  volt  is  changed  to  208V;  if  the 
“Select” button is pressed for more than one second, the next flickering string 
“220”  appear,  the  order  of  flickering  string  is  208  –  220  –  230  –  240  –  208, 
Press “Enter” button to confirm the output volt what you want. 

     

 

         

 

 

 

 

 
Exit  the  setting  mode  to  short  touch  the  “Enter”  button;  continue  setting  to 
press  “Select”  button.  if  no  any  pressing  on  the  “Select”  or  “Enter”  button 
lasting for more than 10 seconds, the setting mode exit automatically. 
  The  output  frequency  string  “OPF”,  Bypass  status  string  ”  bYPA”,  operating 
mode  string  “MOdE”,  Battery  string  “bSTR”,  Load  segment  string  “LS1”  and 
“LS2”  would  be  presented  circularly.  The  only  one  voltage  value  could  be 
selected  in  “208V”,  “220V”,  “230V”,  “240V”  at  any  time;  The  only  one 
frequency  value  could  be  selected  in  “50Hz”,  “60Hz”  at  any  time;  Bypass 
status  could  be  selected  in  “000”  or  “001”(Here  000  means  Bypass 
Disable,001  means  Bypass  Enable),The  UPS  would  turn  to  bypass  mode  in 

 

29 

several seconds after “Bypass Enable” is selected, and turn to no output mode 
in several  seconds  after “Bypass  Disable” is selected; Operating  mode could 
be  selected  in  “UPS”,  “ECO”,  “CVF”(Here  “UPS”  means  the  normal  inverter 
mode, “ECO” means the high efficiency mode, and “CVF” means the converter 
mode),  The  mode  change  would  be  active  only  after  the  UPS  is  turned  on; 
Battery string could be selected in “001” to “009”(Here “001” means one group 
battery). Load segment 1 could be selected in “000” or “001”(Here 000 means 
load  segment  1  off,  001  means  load  segment  1  on);  Load  segment  2  is  the 
same as Load segment 1.

 

 

Here  is  a  example  for  changing  the  Operating  mode  from  normal  mode  to 

converter mode through the LCD panel.

 

 
 
 
 
 

 

Step 1: “OPV” after pressing the “Enter” button;            Step 2: “OPF” after pressing the “Select” button. 

 

 
 
 
 
 
 

Step 3: “bYPA” after pressing the “Select” button;      Step 4: “MOdE” after pressing the “Select” button, 

press the “Enter” button to set mode, then “UPS” flickering; 

 

 

 
 
 
 

 

 

Step  5: “ECO” flickering  after pressing  the  “Select”  button;  Step  6:  “CVF” flickering  after  pressing the 

“Select”  button  again. Press the  “Enter”  button  to  make  sure to  change the  mode.  Short touch  “Enter” 

button to exit setting mode. 

Содержание AP160N Series 1000VA

Страница 1: ...iption 17 5 Connection and Operation 19 5 1 Inspection 19 5 2 Connection 19 5 3 Battery charge 21 5 4 Turn on the UPS 21 5 5 Test function 21 5 6 Turn off the UPS 22 5 7 Audible alarm mute function 22...

Страница 2: ...ssure to connect with the earth reliably Assure external battery source must be earthed Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet shockproof socket...

Страница 3: ...the end of the tower 2 Place down the UPS into two stands carefully 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel 5 l Rack mount...

Страница 4: ...battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reas...

Страница 5: ...the gate and then reassemble front panel B C A D E 9 Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the num...

Страница 6: ...alified maintenance personnel 1 3 1 UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the s...

Страница 7: ...ake on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the I button 1 second to start the battery test on line mode or...

Страница 8: ...D IEC EN 61000 4 2 Level 3 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 1...

Страница 9: ...KS Extended backup time 17 4 Panel Description The Display Panel Switch Function ON Button Turn on UPS system By pressing the ON Button I the UPS system is turned on Deactivate acoustic alarm By press...

Страница 10: ...orm the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to pre...

Страница 11: ...ed 5 4 Turn on the UPS 1 With utility power connecting Press I button continuously for more than 1 second to turn on the UPS the UPS will get into the inverter mode the LCD screen will indicate the st...

Страница 12: ...will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connecting the battery pack 3 The battery connection procedure is very important Any i...

Страница 13: ...nominal power capacity 25 Note Please follow the following steps to connect the generator l Activate the generator and wait until the operation is stable before supplying power of the generator to th...

Страница 14: ...hile the utility power is in normal range so the high efficiency could be gained in the ECO mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied cont...

Страница 15: ...for more than 10 seconds the setting mode exit automatically The output frequency string OPF Bypass status string bYPA operating mode string MOdE Battery string bSTR Load segment string LS1 and LS2 wo...

Страница 16: ...battery voltage is normal and the mains is normal charge automatically again Battery low Battery voltage is low When audible alarm sounding every second battery is almost empty 31 Charge fail The cha...

Страница 17: ...d start the UPS If it needs to replace the batteries while the UPS is running make sure the UPS would not shut down during the replacement If there is a battery breaker then turn it off first Disconne...

Страница 18: ...a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable...

Страница 19: ...er WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems...

Страница 20: ...1 AC Output 2 EPO Dry input Communication Port 3 USB Port 4 AC Input 5 Dry out 6 SNMP slot 7 RS232 8 Modem Network Surge Protection 9 Earth Line connection 39 1 1 3K Standard model rear panel 3K KS mo...

Отзывы: