10 

Torque force when connecting to terminal block. 

 

Use  No.  10AWG  (for  all  models  battery  wire),  90

°

C  copper  wire  and 

Anderson PP45 connectors for user’s external battery cabinet. 

1.3 Maintenance, servicing and faults 

 

The  UPS  operates  with  hazardous  voltages.  Repairs  may  be  carried  out 

only by qualified maintenance personnel. 

 

Caution - risk of electric shock. Even after the unit is disconnected from the 

mains power supply  (building wiring  socket), components  inside the UPS 

are still connected to the battery which are potentially dangerous. 

 

Before carrying out any kind of service and/or maintenance, disconnect the 

batteries.    Verify  that  no  current  is  present  and  no  hazardous  voltage 

exists in the capacitor or BUS capacitor terminals. 

 

Batteries must be replaced only by qualified personnel. 

 

Caution - risk of electric shock. The battery circuit is not isolated from the 

input  voltage.  Hazardous  voltages  may  occur  between  the  battery 

terminals and the ground. Verify that no voltage is present before servicing! 

 

Batteries have a high short-circuit current and pose a risk of shock.    Take 

all  precautionary  measures  specified  below  and  any  other  measures 

necessary when working with batteries: 

 

  remove all jewellery, wristwatches, rings and other metal objects 

 

  use only tools with insulated grips and handles. 

 

When  changing  batteries,  replace  with  the  same  quantity  and  the  same 

type of batteries. 

 

Do  not  attempt  to  dispose  of  batteries  by  burning  them.  It  could  cause 

explosion. 

 

Do  not  open  or  destroy  batteries.  Effluent  electrolyte  can  cause  injury  to 

the skin and eyes. It may be toxic. 

 

Please replace the fuse only by a fuse of the same type and of the same 

amperage in order to avoid fire hazards. 

 

Do not dismantle the UPS, except the qualified maintenance personnel. 

1.3.1 UPS and Battery Care 

For  the  best  preventive  maintenance,  keep  the  area  around  the  UPS  clean 
and dust-free. If the atmosphere is very dusty, clean the outside of the system 

 

11 

with  a  vacuum  cleaner.  For  long  battery  life,  keep  the  UPS  at  an  ambient 
temperature of 25°C (77°F) 

 

 
 

1.3.2 Storing the UPS and Batteries 

When  the  UPS  is  intended  to  store  for  a  long  period,  recharge  the  battery 
every 6 months by connecting the UPS to utility power. The batteries charge to 
90% capacity in approximately 4 hours. However, it is recommended that the 
batteries charge for 48 hours after long-term storage. 

1.3.3 Time to Replace Batteries 

When the discharging time is less than 50% of specified after full charged, the 
battery  may  need  to  be  replaced.  Please  check  the  battery  connection  or 
contact your local dealer to order new battery. 

 

WARNING:

 

 

l

 

Turn off the UPS and disconnect the utility power cord from the wall outlet. 

l

 

Servicing  should  be  performed  by  qualified  service  personnel 
knowledgeable  of  batteries  and  required  precautions.  Keep  unauthorized 
personnel away from batteries   

l

 

Batteries  can present  a  risk  of  electrical  shock or  burn  from high  short 
circuit current. The following precautions should be observed: 

1. Remove watches, rings, or other metal objects. 
2. Use tools with insulated handles. 
3. Do not lay tools or metal parts on top of batteries. 
4. Wear rubber gloves and boots.   
5.  Disconnect  the  charging  source  prior  to  connecting  or  disconnecting 

battery terminal. 

l

 

When  replacing  batteries,  replace  with  the  same  type  and number  of 
batteries  or  battery  packs.  Contact  your  service  representative  to  order 
new batteries. 

l

 

Do not dispose of battery in a fire. Batteries may explode when exposed to 
flame. 

l

 

Proper  disposal  of  batteries  is  required.  Refer  to  your  local  codes  for 
disposal requirements. 

l

 

Do not open or mutilate the battery. Released toxic electrolyte is harmful to 
skin and eyes. 

 

Содержание AP160N Series 1000VA

Страница 1: ...iption 17 5 Connection and Operation 19 5 1 Inspection 19 5 2 Connection 19 5 3 Battery charge 21 5 4 Turn on the UPS 21 5 5 Test function 21 5 6 Turn off the UPS 22 5 7 Audible alarm mute function 22...

Страница 2: ...ssure to connect with the earth reliably Assure external battery source must be earthed Connect the UPS only to an earthed shockproof socket outlet The building wiring socket outlet shockproof socket...

Страница 3: ...the end of the tower 2 Place down the UPS into two stands carefully 3 Pull out the LCD box and rotate it in a clockwise direction to 90 degree and then push it back in the front panel 5 l Rack mount...

Страница 4: ...battery terminal A from UPS to EBM terminal B shown as below Users need to remove the small gate C on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reas...

Страница 5: ...the gate and then reassemble front panel B C A D E 9 Note Three or more EBMs can be connected to the UPS in the same way as shown above Note After connect the EBMs please do not forget to set the num...

Страница 6: ...alified maintenance personnel 1 3 1 UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the s...

Страница 7: ...ake on off the load To test batteries 1 Connect the UPS to utility power for at least 48 hours to charge the batteries 2 Press and hold the I button 1 second to start the battery test on line mode or...

Страница 8: ...D IEC EN 61000 4 2 Level 3 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips IEC EN 61000 4 1...

Страница 9: ...KS Extended backup time 17 4 Panel Description The Display Panel Switch Function ON Button Turn on UPS system By pressing the ON Button I the UPS system is turned on Deactivate acoustic alarm By press...

Страница 10: ...orm the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to pre...

Страница 11: ...ed 5 4 Turn on the UPS 1 With utility power connecting Press I button continuously for more than 1 second to turn on the UPS the UPS will get into the inverter mode the LCD screen will indicate the st...

Страница 12: ...will cause abnormality or permanent damage 2 One hard wiring type battery terminal on the rear panel is used for connecting the battery pack 3 The battery connection procedure is very important Any i...

Страница 13: ...nominal power capacity 25 Note Please follow the following steps to connect the generator l Activate the generator and wait until the operation is stable before supplying power of the generator to th...

Страница 14: ...hile the utility power is in normal range so the high efficiency could be gained in the ECO mode Once the mains is loss or abnormal the UPS would transfer to battery mode and the load is supplied cont...

Страница 15: ...for more than 10 seconds the setting mode exit automatically The output frequency string OPF Bypass status string bYPA operating mode string MOdE Battery string bSTR Load segment string LS1 and LS2 wo...

Страница 16: ...battery voltage is normal and the mains is normal charge automatically again Battery low Battery voltage is low When audible alarm sounding every second battery is almost empty 31 Charge fail The cha...

Страница 17: ...d start the UPS If it needs to replace the batteries while the UPS is running make sure the UPS would not shut down during the replacement If there is a battery breaker then turn it off first Disconne...

Страница 18: ...a computer connect one end of the serial communication cable that comes with the UPS to the RS 232 port on the UPS Connect the other end of the serial cable to the RS 232 port on a computer The cable...

Страница 19: ...er WinPower is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems...

Страница 20: ...1 AC Output 2 EPO Dry input Communication Port 3 USB Port 4 AC Input 5 Dry out 6 SNMP slot 7 RS232 8 Modem Network Surge Protection 9 Earth Line connection 39 1 1 3K Standard model rear panel 3K KS mo...

Отзывы: