Communication GUI Guide
GXE600 Series
TDK-Lambda
<Page>
39/41
#
Starting Address
Qty. Function
15
PF Count
113
1
Register for PF count setting.
Set the time from when PF is detected until
when the PF signal is actually output.
When the output continues to be below the PF detection threshold for
more than the time set in the PF count register, the PF signal is output.
T he register setting value
Max.
Min.
Factory setting
Unit
Integer data
100
0
0
ms
16
Automatic recovery time
114
1
Register for setting automatic recovery time.
Specify the waiting time until the output returns when
the protection function set for automatic recovery is activated.
If the protection factor continues to occur, the output is shut down
again after the automatic recovery time has elapsed.
T he register setting value
Max.
Min.
Factory setting
Unit
Integer data
1000
100
100
10ms
Factory setting
:
100 x 10 ms = 1 sec
17
Erase Alarm History
115
1
Register for erasing alarm history.
Erase the contents of the alarm history register.
If the protection factor continues, the continuation factor bit
is set again after erasing.
T he register setting value
Erase
No action Factory setting
Unit
Integer data
1
0
-
-
* T his register is write-only.
18
Slave ID
200
1
Register for setting the slave ID.
For each GXE connected to the communication bus line,
a unique slave ID must be set.
Before connecting to the communication bus line,
update this register value.
T he register setting value
Max.
Min.
Factory setting
Unit
Integer data
247
1
1
-
* T o avoid misconfiguration, broadcast updates are ignored.
19
SCI Baud Rate
201
1
Register for communication speed setting.
The communication speed of GXE is specified
by the register value shown below.
T he register setting value
Set the communication speed to 2400 bps.
Set the communication speed to 4800 bps.
Set the communication speed to 9600 bps.
Set the communication speed to 19200 bps. *
*Factory setting
0
1
2
3
Data form
(0x00C8)
Data form
(0x00C9)
Value
Overview
(0x0073)
Holding Register
(0x0071)
Data form
(0x0072)
Data form