Communication GUI Guide

GXE600 Series

TDK-Lambda

<Page>

26/41

4.2.2 Setting of reference value / protection threshold
T he display and editing area has two types of register value notation and register value conversion notation. 
T hey are synchronized.
When you click the [Write] button arranged in each item, the changed data is written to GXE.

Display and edit area (Register value)

Display and edit area (Register conversion value)

[Write] Button

Item

Overview

Difital CV

Set the reference value of the output voltage when the digital CV function is enabled.
In the display area, the left side is the register data 
and the right side is the voltage conversion value.
T he register data is the normalized reference value with the nominal voltage [Q10 format *]
T he register value can be set within the range of 0.0 [Q10] to 1.3 [Q10].
(1.3 times the nominal voltage is the upper limit)
If a value out of upper range is entered, 1.3 [Q10] is set.
Product specifications range from 0.2 to 1.2 times the nominal voltage.
Factory setting : 1.0[Q10]  (1.0 times the nominal value)

Digital CC

Set the reference value of the output current when the digital CC function is enabled.
In the display area, the left side is the register data 
and the right side is the current conversion value.
T he register data is the normalized reference value with the maximum current[Q10 format]
T he register value can be set within the range of 0.0 [Q10] to 1.15 [Q10].
(1.15 times the maximum current is the upper limit)
If a value out of upper range is entered, 1.15 [Q10] is set.
Product specifications range from 0.2 to 1.15 times the maximum current.
Factory setting : 1.15[Q10]  (1.15 times the maximum current)

OVP Threshold

Set detection threshold of SWOVP (software overvoltage protection).
In the display area, the left side is the register data 
and the right side is the voltage conversion value.
Register data is normalized with threshold of nominal voltage [Q10 format]
T he register value can be set within the range of 0.2 [Q10] to 1.25 [Q10].
(1.25 times the nominal voltage is the upper limit)
If a value out of upper range is entered, 1.25 [Q10] is set.
Factory setting : 1.25[Q10]  (1.25 times the nominal voltage)

OCP Threshold

Set detection threshold of SWOCP (software overcurrent protection).
In the display area, the left side is the register data 
and the right side is the current conversion value.
Register data is normalized with threshold of nominal current [Q10 format]
T he register value can be set within the range of 0.2 [Q10] to 1.20 [Q10].
(1.20 times the maximum current is the upper limit)
If a value out of upper range is entered, 1.20 [Q10] is set.
Factory setting : 1.20[Q10]  (1.2 times the nominal current)
T o enable SWOCP, set the threshold smaller the CC reference value.

* For the Q10 format, refer to "5.3 Q format data".

Содержание GXE600 Series

Страница 1: ...t of software itself directly or indirectly causes damage we do not assume any responsibility for the damage We do not be obliged to make corrections and support even if there is a deficiency in this...

Страница 2: ...6 VI Graph Tab 3 7 Multi Monitor Tab 3 8 E CapLife Tab 3 9 Advanced Tab 4 Manual screen mode 4 1 Screen layout 4 1 1 GXE Output 4 1 2 Tab area 4 1 3 Meters 4 1 4 Information display area 4 2 Holding...

Страница 3: ...as been confirmed that Windows 7 64 32 bit and Windows 10 can operate in our environment 1 1 GXE Access Installation GXE Access is provided as a compressed file Zip format After decompressing the comp...

Страница 4: ...ll start Depending on the PC environment it might take about 1 hour to install It might be necessary to restart the PC Please restart the PC following the instructions on the screen After installation...

Страница 5: ...onverter and GXE for information of connector cable wire diameter etc used for connection Connection Be sure to connect CN84 and then USB cable in order After complete the connection apply the input v...

Страница 6: ...communication connection is successful Screen mode Overview Graphical A Graphical screen mode can be operated intuitively It is an application example using GXE In the Graphical screen mode communica...

Страница 7: ...value as GXE to be connected Select from None No Parity Odd Odd Parity and Even Even Parity Factory setting Even Timeout Set the timeout time 100 to 2000 ms for communication error The default value i...

Страница 8: ...If the tab is not displayed refer to 2 2 Connection setting The necessary settings can be set automatically by Automatic Settings button The setting item changed by Automatic Settings button can be re...

Страница 9: ...ion tab The tab has the following structure Tab Overview GUI Configuration Display communication setting and information on connected GXE PS Configuration PS Configuration tab has items necessary to o...

Страница 10: ...tNo Serial No Displays the lot number and serial number of the connected GXE 5 Life of Displays the predicted remaining time for electrolytic capacitor Lo in percent Electrolytic Capacitor For details...

Страница 11: ...umerical value and these are synchronized Slide bar accepts mouse operation Numeric value input field is available with keyboard 15 Over current Indicates protection operation mode at Over current The...

Страница 12: ...nication was disconnected 1 Communication tool settings 2 GUI Version 3 Connected GXE 4 Temperature notation Item Overview 1 Communication tool settings For the communication tool setting field refer...

Страница 13: ...are ignored Analog GXE works on the reference of output voltage variable volume and the external voltage to the PV or CC terminal Digital GXE works on the reference by communication CV CC target 3 Co...

Страница 14: ...The graph is updated even when Trend Graph tab is not selected 1 Output voltage current axis 2 GXE internal temperature axis 3 Graph legends Item Overview 1 Output voltage current Scale for output vol...

Страница 15: ...100 Vac If input is less than 100 Vac please check the instruction manual Mounting Select the installation direction of GXE Refer to Mounting type legend Cover Select the presence or absence of the o...

Страница 16: ...he monitored output voltage 4 Output current indication Displays the monitored output current 5 Internal Temperture Displays the monitored internal temperture indication 6 Alarm history indication Dis...

Страница 17: ...e the remaining life is indicated by The denominator is the initial value The initial value is different for each voltage model but it is automatically discriminated Initial value 24V 8000 hour 48V 10...

Страница 18: ...layed in the setting item list 3 Load button It is a button to read the setting list data saved on the PC When you click Load button a dialog will be displayed and you can select the target to be read...

Страница 19: ...disconnection it becomes the GUI Configuration tab of the Graphical screen mode 3 Unit ID Displaying the ID of the connected GXE It is also possible to change the connection destination by changing t...

Страница 20: ...Remote On Issue a remote On query to the volatile non volatile register displayed in the control register Remote Off Issue a remote Off query to the volatile non volatile register displayed in the co...

Страница 21: ...tomatic restoration Operation Time The cumulative operating time of the GXE is displayed not including Remote off time E cap L0 Remain The predicted lifetime of the electrolytic capacitor inside the p...

Страница 22: ...th the OVP threshold register Factory setting 125 Typ of the nominal voltage HWOVP Indication that output overvoltage was detected between output terminals between V and V terminals Detection level ca...

Страница 23: ...se radix is displayed at the left end of the display area it is possible to change the display radix by clicking the radix part For details on the display radix see 4 1 3 Meters The display data can b...

Страница 24: ...is used as the remote control signal In Mixed RC mode the GXE output only when both analog RC and digital RC are remote ON Debounce Count Sets the filter time for removing the debounce of the analog C...

Страница 25: ...in check box format Checked When the protection function operates the output of the power supply will be latched off To reset the latched off the remote Off to On or re input the power source are req...

Страница 26: ...normalized reference value with the maximum current Q10 format The register value can be set within the range of 0 0 Q10 to 1 15 Q10 1 15 times the maximum current is the upper limit If a value out o...

Страница 27: ...red for the CV reference value to change from 0 to 100 The set time is applied when the next AC turn on or remote control turns OFF ON Register value can be set in the range of 20 ms to 10000 ms facto...

Страница 28: ...ton to display the device settings of GXE All data all at once Clicking the individual Write button updates the setting value of GXE to the edited data GXE SCI Settings Use to change the communication...

Страница 29: ...actually output Setting the PF count prevents the PF signal from being erroneously output due to noise or the like The value can be set in the range of 0 x 1 ms to 100 x 1 ms Factory setting 0 count 0...

Страница 30: ...47 Factory setting 1 Baud Rate bps Set the Baud Rate of GXE Click the display area and select the Baud Rate Select Baud Rate from 2400 4800 9600 and 19200 bps Factory setting 19200 Parity Bit Set the...

Страница 31: ...eg3 tab the screen of Holding Reg 3 will be displayed 1 Scratch Pad 1 2 Scratch Pad 2 Item Overview Scratch Pad 1 Scratch Pad 2 The scratch pad is a register that you can store data freely By clicking...

Страница 32: ...e screen There is no saved data at factory shipment Write Button Display style setting Display and edit area Read Button In the display area data of 30 characters or less in ASCII characters can be sa...

Страница 33: ...is displayed in each item of the display area Display area Read Button The following data is displayed on the screen Item Overview Model Name The model name registered in the product is displayed Seri...

Страница 34: ...hat overtemperature protection has been activated Indicates that the booster output inside the power supply has decreased Reserved bit Alarm is not allocated Indicates that the power supply is remote...

Страница 35: ...nput shutdown is applied at next input Common items of volatile nonvolatile registers Remote control of GXE output by writing the reference value to the register The register setting value Value Funct...

Страница 36: ...used as the remote control signal Output is turned On when both inputs are remote On Volatile remote On Off registers are not referenced Filter sensitivity Bounce chattering may occur due to the inpu...

Страница 37: ...tual change in output is in accordance with the set value The register setting value Max Min Factory setting Unit Q10 format data 1 3 0 1 0 Integer notation 1331 0 1024 6 CC Digital Reference 104 1 Re...

Страница 38: ...lew rate dv dt at steady output The register setting value Max Min Factory setting Unit Integer data 10000 20 20 ms 12 CC Transition Time 110 1 Register for setting CC reference value slew rate at ste...

Страница 39: ...tory 115 1 Register for erasing alarm history Erase the contents of the alarm history register If the protection factor continues the continuation factor bit is set again after erasing The register se...

Страница 40: ...re set Odd parity it is set to 1 stop bit Even parity it is set to 1 stop bit Factory setting 21 Scratch Pad 1 300 15 Register for scratchpad 1 Scratch Pad 2 320 15 Register for scratchpad 2 Common it...

Страница 41: ...1001 1001 It becomes a circulating binary decimal of 1100 from the bit weight of 2 4 Returning the value of this binary number to decimal number it will be 0 0999908447265625 it will not be exact 0 1...

Отзывы: