POINT CHECK
The POINT CHECK menu is used to check the operation of individual components. Use
▼▲
to scroll to the components
you want to check and press COMFIRM to toggle the on/off state of the component. If a valve does not turn on/off when
its on/off state is toggled or if a pump/heater does not operate when turned on, check the component’s connection to the
hydronic system main PCB.
POINT CHECK menu
1.14.2
AIR PURGE operation
MENU > FOR SERVICEMAN > TEST RUN > AIR PURGE
Once installation is complete it is important to run the air purge function to remove any air which may be present in the
water piping and which could cause malfunctions during operation.
The AIR PURGE operation is used to remove air from the water piping. Before running AIR PURGE mode, make sure that
the air purge valve is open. PUMPI will run according to the output and running time that has been set
1.14.3
CIRCULATED PUMP RUNNING operation
MENU > FOR SERVICEMAN > TEST RUN > CIRCULATED PUMP RUNNING
CIRCULATED PUMP RUNNING operation is used to check the operation of the
circulation pump. When circulation pump running is turned on, all running
components will stop. 60 seconds later, the SV1 will be off, the SV2 will be on, 60
seconds later PUMPI will operate. 30s later, if the flow switch checked normal flow,
PUMPI will operate for 3min, after the pump stops 60 seconds, the SV1 will close
and the SV2 will be off. 60s later the both PUMPI and PUMPO will operate, 2 mins
later, the flow switch will check the water flow. If the flow switch closes for 15s,
PUMPI and PUMPO will operate until the next command is received.
11 TEST RUN
OFF
OFF
OFF
OFF
OFF
1/3
SV2
SV3
PUMPI
PUMPO
PUMPC
ON/OFF
11 TEST RUN
OFF
OFF
OFF
OFF
OFF
IBH
AHS
SV1
PUMPD
PUMPS
2/3
ON/OFF
11 TEST RUN
OFF
TBH
3/3
ON/OFF
AIR PURGE operation
CIRCULATION PUMP RUNNING display
11 TEST RUN(POINT CHECK)
AIR PURGE PUMPI OUTPUT
AIR PURGE RUNNING TIME
70%
20min
CONFIRM
ENTER
EXIT
11 TEST RUN
TEST RUN IS ON.
CIRCULATED PUMP IS ON.
CONFIRM