62
1.3
FOR SERVICEMAN Menu
FOR SERVICEMAN allows installers to input the system configuration and set the
system parameters. To enter FOR SERVICEMAN, go to MENU > FOR SERVICEMAN.
Enter the password, using
◄
►
to navigate between digits and using
▼
▲
to adjust
the numerical values. The password is 234.
Then the following pages will be displayed after putting the password.
FOR SERVICEMAN menu
1.4
DHW MODE SETTING Menu
1.4.1
DHW MODE SETTING menu overview
MENU > FOR SERVICEMAN > DHW MODE SETTING
DHW MODE SETTING menu
DHW MODE enables or disables DHW mode. For installations with DHW tanks, select YES to enable DHW mode. For
installations without DHW tanks, select NON to disable DHW mode.
DISINFECT sets whether or not the disinfection operation is performed.
DHW PRIORITY sets whether domestic hot water heating or space heating/cooling takes priority. If NON is selected in the
DHW PRIORITY mode, heat pump will change from DHW mode to heating/cooling mode immediately if heating/cooling
ENTER
FOR SERVICEMAN
1. DHW MODE SETTING
2. COOL MODE SETTING
3. HEAT MODE SETTING
4. AUTO MODE SETTING
5. TEMP.TYPE SETTING
6. ROOM THERMOSTAT
1/3
7. OTHER HEATING SOURCE
8. HOLIDAY AWAY SETTING
TING
9. SERVICE CALL SETTING
10. RESTORE FACTORY SETTINGS
11. TEST RUN
12. SPECIAL FUNCTION
ENTER
FOR SERVICEMAN
2/3
ENTER
FOR SERVICEMAN
13. AUTO RESTART
14. POWER INPUT LIMITATION
15. INPUT DEFINE
16. CASCADE SET
17. HMI ADDRESS SET
18. COMMON SET
3/3
1 DHW MODE SETTING
YES
YES
YES
YES
NON
ADJUST
1.1 DHW MODE
1.2 DISINFECT
1.3 DHW PRIORITY
1.4 PUMP_D
1.5 DHW PRIORITY TIME SET
1/4
5
°C
10°C
43°C
-10°C
5 MIN
1 DHW MODE SETTING
1.6 dT5_ON
1.7 dT1S5
1.8 T4DHWMAX
1.9 T4DHWMIN
1.10 t_INTERVAL_DHW
2/4
ADJUST
°C
15MIN
210 MIN
30MIN
120MIN
1 DHW MODE SETTING
1.11 T5S_DISINFECT
1.12 t_DI_HIGHTEMP.
1.13 t_DI_MAX
1.14 t_DHWHP_RESTRICT
1.15 t_DHWHP_MAX
ADJUST
3/4
65
YES
5 MIN
NON
NON
1 DHW MODE SETTING
1.16 PUMP_D TIMER
1.17 PUMP_D RUNNING TIME
1.18 PUMP_D DISINFECT
1.19 ACS FUNCTION
4/4
ADJUST