70
dT1_IBH_ON sets the temperature difference between the heat pump leaving water set temperature (T1S) and the heat
pump leaving water temperature (T1) above which the backup electric heater is on. When T1S - T1 ≥ dT1_IBH_ON the
backup electric heater is on.
t_IBH_DELAY sets the delay time for the electric heater to turn on after the compressor starts.
T4_IBH_ON sets the ambient temperature below which the
backup electric heater is on.
P_IBH1 sets heating capacity of IBH1, which is used for energy consumption statistics.
P_IBH2 sets heating capacity of IBH2, which is used for energy consumption statistics.
AHS FUNCTION sets enable or disable the additional heating source function.
AHS_PUMPI CONTROL select the pump operating status when only AHS runs
dT1_ASH_ON sets the temperature difference between the heat pump leaving water set temperature (T1S) and the heat
pump leaving water temperature (T1) above which the additional heating source is on. When T1S - T1 ≥ dT1_AHS_ON the
additional heating source is on.
t_ASH_DELAY sets the delay time for the AHS to turn on after the compressor starts.
T4_AHS_ON sets the ambient temperature below which the additional heating source is on.
EnSWITCHPDC
enable or disable the function that heat pump and additional heating source switch automatically based on
running cost
GAS_COST set the price of gas
ELE_COST set the price of electricity
MAX_SETHEATER sets the maximum temperature of additional heating source.
MIN_SETHEATER sets the minimum temperature of additional heating source.
MAX_SIGHEATER sets the voltage corresponding to the maximum setting temperature of additional heating source
MIN_SIGHEATER sets the voltage corresponding to the minimum setting temperature of additional heating source
T4_IBH_ON
Abreviations:
T4: Outdoor ambient temperature
IBH: Backup electric heater
T4_AHS_ON
Abreviations:
AHS:
Additional heating source
T4: Outdoor ambient temperature