71
TBH FUNCTION enable or disable tank booster heater.
dT5_TBH_OFF sets the temperature difference between the DHW set temperature (T5S) and the DHW tank water
temperature (T5) below which the tank booster heater is not used. When T5 > Min(
T5S+
dT5_TBH_OFF, 65°C), the tank
booster heater is off.
t_TBH_DELAY sets the delay time for the tank booster heater to turn on after the compressor starts.
T4_TBH_ON sets the ambient temperature above which the tank booster heater will not be used.
P_TBH set the input power of tank booster heater.
SOLAR FUNCTION
enable or disable the SOLAR function to produce hot water
SOLAR CONTROL
set the control method of solar. (Tsolar temperature sensor or SL1SL2 port on hydro module PCB)
DELTASOL
sets the deviation temperature that SOLAR turns on
1.11
HOLIDAY AWAY SETTING Menu
MENU > FOR SERVICEMAN > HOLIDAY AWAY SETTING
The HOLIDAY AWAY SETTING menu settings are used to set the outlet water
temperature to prevent water pipes freezing when away from home in cold weather
seasons.
T1S_H.A._H sets the heat pump leaving water set temperature for space heating
mode when in holiday away mode.
T5S_H.M_DHW sets the heat pump leaving water set temperature for DHW mode
when in holiday away mode.
1.12
SERVICE CALL Menu
MENU > FOR SERVICEMAN > SERVICE CALL
PHONE NO. and MOBILE NO. can be used to set after-sales service contact numbers. Use
▼
▲
to adjust the numerical
values. The maximum length of the phone numbers is 13 digits.
HOLIDAY AWAY SETTING menu
SERVICE CALL menu
20°C
20
°C
8 HOLIDAY AWAY SETTING
8.1 T1S_H.A._H
8.2 T5S_H.A._DHW
ADJUST
ADJUST
CONFIRM
9 SERVICE CALL SETTING
PHONE NO.
0
000000000000
MOBILE NO. 0000000000000