dTSH sets the temperature difference between the actual room temperature (Ta) and set room temperature (TS) above
which the heat pump provides hot water to the space heating terminals. When TS – Ta ≥ dTSH the heat pump provides hot
water to the space heating terminals and when Ta ≥ TS the heat pump does not provide hot water to the space heating
terminals. dTSH is only relevant if YES is selected for ROOM TEMP in the 5 TEMP. TYPE SETTING menu.
Ta+dTSH
HEATING ON
TS
Ta
HEATING OFF
t_INTERVAL_H sets the heating mode compressor re-start delay. When the compressor stops running, it will not re-start
until at least t_INTERVAL_H minutes have elapsed.
T1SetH1 sets the water temperature 1 of automatic setting curve for heating mode.
T1SetH2 sets the water temperature 2 of automatic setting curve for heating mode.
T4H1 sets the ambient temperature 1 of automatic setting curve for heating mode.
T4H2 sets the ambient temperature 2 of automatic setting curve for heating mode.
ZONE1 H-EMISSION sets the emission type for heating mode. (FCU: Fan coil unit; FHL: Floor heating loop; RAD.: Radiator)
ZONE2 H-EMISSION sets the emission type for heating mode. (FCU: Fan coil unit; FHL: Floor heating loop; RAD.: Radiator)
FORCE DEFROST enable heat pump enters defrost mode by manual operation when heat pump runs for 10min and air side
heat exchanger outlet temperature T3<0
℃
lasts for more than 6min.
1.7
AUTO MODE SETTING Menu
MENU > FOR SERVICEMAN > AUTO MODE SETTING
T4AUTOCMIN sets the ambient temperature below which the heat pump will not
provide chilled water for space cooling in auto mode.
T4AUTOHMAX sets the ambient temperature above which the heat pump will not
provide hot water for space heating in auto mode.
T4AUTOCMAX, T4AUTOCMIN
Abreviations:
AHS: Additional heating source
IBH: Backup electric heater
T4CMAX: The ambient temperature above which the heat pump will not
operate in cooling mode.
T4HMIN: The ambient temperature below which the heat pump will not
operate in heating mode.
AUTO MODE SETTING menu
17°C
25
°C
4 AUTO. MODE SETTING
4.1 T4AUTOCMIN
4.2 T4AUTOHMAX
ADJUST