49
7
Sound Levels
7.1
Overall
Table 2‐8.1: Sound pressure levels
1
Model name
dB(A)
2
SYSHP MINI 05 EVO‐P Q
48
SYSHP MINI 0
7
EVO‐P Q
51
SYSHP MINI 0
9
EVO‐P Q
53
SYSHP MINI
12
EVO‐P Q
56
SYSHP MINI
14
EVO‐P Q
58
SYSHP MINI
16
EVO‐P Q
58
SYSHP MINI
12
EVO‐P R
57
SYSHP MINI
14
EVO‐P R
59
SYSHP MINI
16
EVO‐P R
59
Notes:
1.
Sound pressure level is measured at a position 1m in front of the unit and (1+H)/2m (where H is the height of the unit) above the floor in a semi‐anechoic
chamber. During in‐situ operation, sound pressure levels may be higher as a result of ambient noise.
Figure 2‐8.1: Sound pressure level measurement (unit: mm)
2.
dB(A) is the maximum value tested under the conditions below:
Outdoor air temperature 7⁰C DB, 6⁰C WB; EWT 30⁰C, LWT 35⁰C. Free compressor frequency.
Outdoor air temperature 7⁰C DB, 6⁰C WB; EWT 47⁰C, LWT 55⁰C. Free compressor frequency.
1000
(H+1000)
2
Front
Содержание SYSHP MINI 05 EVO-P Q
Страница 3: ...2 ...
Страница 59: ...58 ...
Страница 60: ...59 Part 3 Installation and Field Settings 1 User Interface Field Settings 60 2 Operation parameter 79 ...
Страница 82: ......