76
Phase 1: gradual temperature increase from a starting point of 25°C to the peak temperature
Phase 2: maintain peak temperature
Phase 3: gradual temperature decrease from the peak temperature to 45°C
WARM UP TIME(t_DRYUP) sets the duration of Phase 1.
KEEP TIME(t_HIGHPEAK) sets the duration of Phase 2.
TEMP. DOWN TIME(t_DRYD) sets the duration of Phase 3.
PEAK TEMP.(T_DRYPEAK) sets the heat pump leaving water set temperature
for Phase 2.
START TIME sets the floor drying up operation start time.
START DATE sets the floor drying up operation start date.
During the floor drying up operation all buttons except OK are inactivated. To exit the floor drying up operation, press OK
and then select YES when prompted.
Note: In the event of a heat pump malfunction, floor drying up mode will continue if a backup electric heater and/or
additional heating source is available and configured to support space heating mode.
1.16
AUTO RESTART
MENU > FOR SERVICEMAN > AUTO RESTART
AUTO RESTART sets whether or not the unit re-applies the user interface settings
when the power returns following a power failure. Select YES to enable auto restart or
NON to disable auto restart.
1.17
POWER INPUT LIMITATION
MENU > FOR SERVICEMAN > POWER INPUT LIMITATION
POWER INPUT LIMITATION sets the type of
power input limitation and the
setting range is 1-8. If the unit will operate at larger power input, 1 should be
selected. If the unit will operate at a lower power input, 2-8 should be selected and
the power input and capacity will decrease.
Model No. 1
2
3
4
5
6
7
8
5/7/9kW
16 15 14 13 12 11 10 9
12/14/16kW(1N)
28 26 24 22 20 18 16 14
12/14/16kW(3N)
11 10 9
8
7
6
5
5
FLOOR DRYING UP settings
AUTO RESTART menu
POWER INPUT LIMITATION
Limitation value (unit:A)
13 AUTO RESTART
YES
YES
ADJUST
13.1 COOL/HEAT MODE
13.2 DHW MODE
14 POWER INPUT LIMITATION
0
ADJUST
14.1POWER INPUT LIMITATION