14
Model
SYSHP MINI
12
EVOP R
14
EVOP R
16
EVOP R
Power supply(V/Ph/Hz)
380-415/3/50
380-415/3/50
380-415/3/50
Heating A7W35
Capacity
W
12200
14100
16000
Rated input
W
2490
3000
3556
COP
4.90
4.70
4.50
Heating A7W45
Capacity
W
12500
14500
16200
Rated input
W
3378
4085
4696
COP
3.70
3.55
3.45
Heating A7W55
Capacity
W
12000
14000
16000
Rated input
W
4000
4746
5614
COP
3.00
2.95
2.85
Heating A2W35
Capacity
W
12300
13000
14500
Rated input
W
3417
3714
4462
COP
3.60
3.50
3.25
Heating A2W45
Capacity
W
12000
13000
14300
Rated input
W
4138
4643
5296
COP
2.90
2.80
2.70
Heating A2W55
Capacity
W
12000
13000
13500
Rated input
W
5106
5603
5870
COP
2.35
2.32
2.30
Heating A-7W35
Capacity
W
11600
12500
13500
Rated input
W
4070
4464
5000
COP
2.85
2.80
2.70
Heating A-7W45
Capacity
W
11500
12500
13500
Rated input
W
4792
5435
6000
COP
2.40
2.30
2.25
Heating A-7W55
Capacity
W
10800
11700
12800
Rated input
W
5143
5625
6244
COP
2.10
2.08
2.05
Cooling A35W18
Capacity
W
12200
13900
15400
Rated input
W
2652
3159
3667
COP
4.60
4.40
4.20
Cooling A35W7
Capacity
W
11600
13400
14000
Rated input
W
3742
4573
4828
COP
3.10
2.93
2.90
Seasonal space heating energy
efficiency class
Water outlet at 35
⁰
C
A+++
A+++
A+++
Water outlet at 55
⁰
C
A++
A++
A++
SCOP
Warmer climate
35
⁰
C
6.64
6.59
6.46
55
⁰
C
4.55
4.64
4.72
Average climate
35
⁰
C
5.08
4.89
4.84
55
⁰
C
3.62
3.62
3.59
Colder climate
35
⁰
C
4.30
4.36
4.35
55
⁰
C
3.23
3.24
3.18
SEER
Water outlet at 35
℃
5.11
5.12
5.14
Water outlet at 55
℃
7.86
7.65
7.54
Содержание SYSHP MINI 05 EVO-P Q
Страница 3: ...2 ...
Страница 59: ...58 ...
Страница 60: ...59 Part 3 Installation and Field Settings 1 User Interface Field Settings 60 2 Operation parameter 79 ...
Страница 82: ......