47
r.3.3
Bag
filters
Release
the
bag
filter
cells
by
activating
the
handles
and
pull
out
the
filter
cells
of
the
unit
casing.
The
frame
profiles
are
to
be
cleaned
and
all
seals
checked
for
damage.
The
handles
and
locking
guide
rails
are
also
to
be
checked
to
ensure
that
they
can
operate
unobstructed.
The
new
filter
bags
must
be
pushed
carefully
into
the
unit
in
order
to
ensure
that
they
are
sealed
properly.
The
various
filter
sizes
should
be
placed
in
an
order
corresponding
to
the
way
in
which
the
unit
is
designed,
and
the
filters
must
have
vertical
bags.
r.3.4
Panel
filters
The
filter
cell
guide
rails
are
to
be
cleaned
before
fitting
the
new
filters.
r.
4
Other
functions
to
maintain
r.
4.1
The
unit
The
unit
should
be
cleaned
once
a
year
when
operating
with
normal
air
quality
for
comfort
ventilation
with
no
special
hygiene
requirements.
To
clean
the
unit,
dry
it
off
with
a
dry
cloth,
or
use
water
mixed
with
a
non
‐
corrosive
cleaning
medium.
Any
corrosion
i.e.
at
the
filters
should
be
cleaned
off
immediately,
and
the
surface
treated.
In
special
operating
conditions,
where
the
air
is
aggressive
or
very
humid,
for
example,
or
where
there
are
special
hygiene
requirements,
the
unit
shall
be
cleaned
more
frequently
as
required.
Cleaning
medium
and
method
should
be
adapted
to
the
relevant
conditions.
Any
corrosion
should
be
cleaned
off
immediately,
and
the
surface
treated.
Closing
mechanisms
are
to
be
lubricated
at
least
once
a
year.
Synthetic
door
hinges
are
service
free.
Seals
around
inspection
doors
are
to
be
cleaned
at
least
once
a
year
and
are
to
be
checked
for
leakage.
It
is
recommended
to
treat
the
seals
with
a
moisture
repellent
agent.
Connecting
pieces
for
the
unit
sections,
including
the
Disc
‐
Lock
types,
are
to
be
checked
for
tightness
at
least
once
a
year.
All
seals
are
to
be
inspected
at
least
once
a
year
and
are
to
be
repaired
if
necessary.
Grilles
for
air
intake
and
exhaust
air
outlet
are
to
be
cleaned
at
least
once
a
year
to
prevent
blockage.
Содержание Danvent DV-10
Страница 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Страница 57: ...56...
Страница 58: ...57 Annex for the User Manual Air Handling Units Danvent DV Without control system Version 1 01 13...
Страница 84: ...8 8...
Страница 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Страница 91: ...9 7...
Страница 92: ...9 8 A1 Size Quantity Length mm DV 60 4 1014 DV 80 4 1164 DV 100 4 1314 DV 120 4 1464 DV 150 4 1614 A1...
Страница 94: ...9 10 9 3 Assemble divided rotor from Hoval Enventus for DV 60 DV 80 and DV 100 9 3 1 Tools and aids 0 100Nm 3 3...
Страница 103: ...9 19...
Страница 111: ...12 3...
Страница 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Страница 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...