32
i.4.5
Draining
condensate
water
Drip
trays
for
collection
of
condensate
water
are
installed
under
plate
heat
exchanger
and
cooling
coil.
Each
drip
tray
is
provided
with
a
drainage
outlet.
A
water
trap
is
always
necessary.
To
avoid
freeze
ups
and
frost
bursts
of
water
trap
and
pipes,
sufficient
insulation
is
recommended
and
installation
of
heating
between
the
insulation
and
water
trap/pipes
could
even
be
necessary
(insulation,
heating
and
controller
for
the
heating
are
not
delivered
by
Systemair).
i.4.6
Draining
condensate
water
from
plate
heat
exchanger
Condensate
from
the
plate
heat
exchanger
is
collected
in
the
drip
tray.
Heavy
negative
air
pressure
in
this
section
prevents
the
water
from
flowing
out
of
the
drainpipe.
A
water
trap
with
sufficient
closing
level
of
the
water
is
essential
to
ensure
that
condensate
water
flows
out
of
the
unit.
The
closing
level
of
the
water
trap
must
be
estimated
correctly
to
ensure
safe
escape
of
the
water
(see
the
illustration
and
estimate
the
minimum
closing
level
according
to
the
table).The
pipe
diameter
of
the
water
trap
and
sewage
system
must
be
identical
to
the
pipe
diameter
of
the
drainage
outlet
from
the
tray.
A
water
trap
is
optional
and
installation
of
the
water
trap
is
not
included.
Remember
to
check
that
there
is
water
in
the
water
trap.
Negative
pressure
P
(Pa)
i.4.7
Draining
condensate
water
from
cooling
battery
If
the
cooling
battery
and
the
drip
tray
is
placed
in
the
unit
where
negative
pressure
(underpressure)
occurs,
the
closing
level
of
the
water
trap
must
be
estimated
correctly.
See
the
above
‐
mentioned
information
in
section
i.4.6
–
Draining
condensate
water
from
the
plate
heat
exchanger.
If
the
cooling
battery
and
the
drip
tray
is
placed
in
the
unit
where
positive
pressure
(overpressure)
occurs,
the
closing
level
of
the
water
trap
must
be
estimated
correctly
as
shown
on
the
illustration
below.
A
water
trap
is
optional
and
installation
of
the
water
trap
is
not
included.
Remember
to
check
that
there
is
water
in
the
water
trap.
Positive
pressure
P
(Pa)
P
H1
Minimum
H2
500
Pa
100
mm
40
mm
750
Pa
150
mm
55
mm
1.000
Pa
190
mm
70
mm
P
H1
Minimum
H2
500
Pa
90
mm
65
mm
750
Pa
120
mm
90
mm
1.000
Pa
150
mm
120
mm
Содержание Danvent DV-10
Страница 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Страница 57: ...56...
Страница 58: ...57 Annex for the User Manual Air Handling Units Danvent DV Without control system Version 1 01 13...
Страница 84: ...8 8...
Страница 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Страница 91: ...9 7...
Страница 92: ...9 8 A1 Size Quantity Length mm DV 60 4 1014 DV 80 4 1164 DV 100 4 1314 DV 120 4 1464 DV 150 4 1614 A1...
Страница 94: ...9 10 9 3 Assemble divided rotor from Hoval Enventus for DV 60 DV 80 and DV 100 9 3 1 Tools and aids 0 100Nm 3 3...
Страница 103: ...9 19...
Страница 111: ...12 3...
Страница 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Страница 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...