12—9
Residual
‐
current
‐
operated
protective
devices
Terminal
Function / connection
L1, N, PE
Mains connection for 1 ~ types (observe the line voltage indicated
rating plate).
L1, L2, L3, PE
Mains connection for 3 ~ types (observe the line voltage indicated
rating plate).
11, 14
Relay output “K1” for fault indication.
*
•
For operation the relay is energized,
connections
“11”
and
“14”
are bridged. For fault the relay
is de-energized (
Diagnostics / faults).
•
When switching off via enable (D1 = Digital In 1), the relay remains
energized.
E1, GND
Analog input for setting speed via 0 - 10 V or PWM signal
*
10V
Voltage supply for speed setting by 10 k
Ω
potentiometer.
24V
Voltage supply for external devices.
D1, +24V
Digital input for enable.
*
•
Device
“ON”
for closed contact.
•
Controller
“OFF”
with opened contact.
*Function
for
standard
factory
setting,
different
presetting
possible.
UL:
Input
(Line)
•
Cu connection leads with the following specifications must be employed:
– Minimum insulation temperature of 80 °C
– Terminal tightening torque for field block (L1, N, and/or L1, L2, L3) of 5 - 7 Lb In.
(Exception: spring-cage terminal for motor size "G" @ line voltage 3 ~ 200...240 V) – Terminal tightening
torque of 4.5 Lb In for field block (K1).
– Terminal tightening torque of 4.5 Lb In for all other field blocks.
– Terminal tightening torque of 2.2 Lb In for add-on modules.
12.5.2
Diagnostic/faults
Status Out with flash code
Содержание Danvent DV-10
Страница 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Страница 57: ...56...
Страница 58: ...57 Annex for the User Manual Air Handling Units Danvent DV Without control system Version 1 01 13...
Страница 84: ...8 8...
Страница 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Страница 91: ...9 7...
Страница 92: ...9 8 A1 Size Quantity Length mm DV 60 4 1014 DV 80 4 1164 DV 100 4 1314 DV 120 4 1464 DV 150 4 1614 A1...
Страница 94: ...9 10 9 3 Assemble divided rotor from Hoval Enventus for DV 60 DV 80 and DV 100 9 3 1 Tools and aids 0 100Nm 3 3...
Страница 103: ...9 19...
Страница 111: ...12 3...
Страница 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Страница 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...