12—5
12.4
Set
‐
up
Danfoss
FC101
for
DV
‐
units
with
PM
motors
SETUP
IS
DONE
IN
FACTORY
BEFORE
DELIVERY
To
reload
Systemair
factory
settings
from
the
control
panel:
0
‐
50:
LCP
Copy:
[2]
Systemair
factory
set
‐
up
is
based
on
Danfoss
initialization.
14
‐
22:
Operation
mode:
[2]
Initialisation
(Danfoss
Initialisation)
Turn
power
off
and
on.
Systemair
factory
set
‐
up:
0
‐
01:
Language
selection:
1
‐
06:
Clockwise
Direction:
[1]
Inverse
1
‐
10:
Motor
Construction:
[1]
PM,
non
‐
salient
SPM
1
‐
24:
Motor
Current:
According
to
motor
plate
/
Schedule
1
‐
25:
Motor
Nominal
Speed:
According
to
motor
plate
/
Schedule
1
‐
26:
Motor
Cont.
Rated
torque:
According
to
motor
plate
/
Schedule
1
‐
30:
Stator
Resistance
(Rs):
According
to
motor
plate
/
Schedule
1
‐
37:
d
‐
axis
inductance
(Ld):
According
to
motor
plate
/
Schedule
1
‐
39:
Motor
Poles:
According
to
motor
plate
/
Schedule
1
‐
40:
Back
EMF
at
1000
RPM:
According
to
motor
plate
/
Schedule
1
‐
42:
Motor
Cable
Length:
3m
1
‐
73:
Flying
start:
[1]
Enabled
1
‐
90:
Motor
Thermal
Protection:
[2]
Thermistor
trip
3
‐
15:
Reference
1
Source:
[2]
Analog
input
AI54
1
‐
93:
Thermistor
Source:
[1]
Analog
input
AI53
3
‐
03:
Maximum
Reference:
According
to
motor
plate
/
Schedule
3
‐
16
+
3
‐
17:
Reference
2
‐
and
3
Source:
[0]
No
function
3
‐
41:
Ramp
1
Up:
According
to
schedule
for
PM
motor
parameters
‐
below
3
‐
42:
Ramp
1
down:
According
to
schedule
for
PM
motor
parameters
‐
below
4
‐
19:
Max.
Output
Frequency:
According
to
motor
plate
/
Schedule
4
‐
14:
Motor
Speed
High
Limit:
According
to
motor
plate
/
Schedule
5
‐
12:
Terminal
27
Digital
input:
[0]
No
operation
5
‐
40.0:
Function
Relay:
[3]
Drive
ready/remote
5
‐
40.1:
Function
Relay:
[3]
Drive
ready/remote
6
‐
25:
Terminal
54
High
Reference:
According
to
motor
plate
/
Schedule
14
‐
20:
Reset
Mode:
[2]
Automatic
reset
x
2
2
‐
01:
DC
brake
current:
100
%
2
‐
02:
DC
braking
time:
20.0
sec.
2
‐
07:
Parking
time:
10,0
sec.
0
‐
50:
LCP
Copy:
[1]
All
to
LCP
(Copy
of
Systemair
factory
settings
to
panel)
Connections:
0
‐
10V:
Terminal
54
‐
55
and
Start:
Terminal
12
‐
18
as
well
as
Thermistor:
Terminal
50
‐
53
Drive
ready:
Terminal
1
‐
2
Содержание Danvent DV-10
Страница 16: ...15 DVE Plug fan DVD Silencer DVX Humidifier...
Страница 57: ...56...
Страница 58: ...57 Annex for the User Manual Air Handling Units Danvent DV Without control system Version 1 01 13...
Страница 84: ...8 8...
Страница 88: ...9 4 9 1 3 Information about connection of cables to terminals on the control board...
Страница 91: ...9 7...
Страница 92: ...9 8 A1 Size Quantity Length mm DV 60 4 1014 DV 80 4 1164 DV 100 4 1314 DV 120 4 1464 DV 150 4 1614 A1...
Страница 94: ...9 10 9 3 Assemble divided rotor from Hoval Enventus for DV 60 DV 80 and DV 100 9 3 1 Tools and aids 0 100Nm 3 3...
Страница 103: ...9 19...
Страница 111: ...12 3...
Страница 115: ...12 7 Frequency converter is always necessary for the control of each PM motor...
Страница 119: ...13 1 Annex 13 Commissioning See separate cover with annexes 1 2 3 and 13...