Piezo
3. System Operation
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
35
Piezo
The piezo (local buzzer) generates different tone patterns for different event conditions:
•
Alarm -
Generates a steady tone, no pulse.
•
Trouble -
Pulses one second on, one second off. Repeats 30 pulses per minute.
•
Supervisory -
Pulses one-half second on, one-half second off. Repeats 60 pulses per minute.
Supervisory Service
Releasing circuit #2 can be used as an input for monitoring supervisory devices (such as valve tamper
switches) by setting SW1 DIP switch 2 to “ON” (see "Setting Mode of Operation" on page 28). After the
panel is programmed for supervisory service, a short circuit on this input (activation of a N.O. contact)
will cause the supervisory LED to flash. The piezo sounder will generate a unique sound. Pressing TONE
SILENCE will silence the piezo and cause the supervisory LED to illuminate steadily. Supervisory signals
latch and require SYSTEM RESET to clear. An open circuit will be reported as a circuit trouble.
Note:
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking operation; latching
operation is the default setting. Canadian regulations require latching operation; for programming instructions, see
"Sprinkler Supervisory Tracking" on page 36.
Zone Disable
If a zone has been disabled, an alarm that occurs on that zone will flash the red zone LED, but not the piezo
or any output circuit.
If both power sources are removed from the system, all zones will be re-enabled upon
restoration of power. Disable status will be lost.
The Zone Disable routine makes use of the four panel
switches as follows: I
1.
Press and hold in the TONE SILENCE switch.
2.
With the TONE SILENCE switch held in, press
(in sequence) the ALARM SILENCE switch, the
ALARM ACTIVATE switch, and then the
SYSTEM RESET switch.
3.
The Zone 1 Alarm LED will flash.
4.
To disable Zone 1, press the SYSTEM RESET switch. The Zone 1 yellow LED will light to show
that the zone is disabled.
Note:
The SYSTEM RESET switch toggles disable status for the selected zone.
5.
To select the next zone, press the ALARM SILENCE switch.
6.
To select the previous zone, press the ALARM ACTIVATE switch.
7.
When disable selections are complete, release the TONE SILENCE switch.
If any zone has been disabled, the trouble relay will activate and System Trouble LED will flash.
T O N E
S IL E N C E
A L A R M
S IL E N C E
A L A R M
A C T IVAT E
S Y S T E M
R E S E T
Press
&
Hold
Press ---> Press ---> Press
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...