PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
47
Appendix C: NFPA Standard-Specific Requirements
Minimum System Requirements
The control panel has been designed for use in commercial, industrial, and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
•
Fire Alarm Control Panel.
Contains the main control board, cabinet (backbox and door), main
supply transformer and power supply.
•
Batteries.
Refer to "Appendix A: Secondary Power Calculations" on page 39
•
Initiating Devices.
Connected to one of the control panel's Initiating Device Circuits.
•
Notification Appliances.
Connected to one of the control panel's Notification Appliance Circuits.
•
Releasing Devices.
Connected to one of the control panel’s Releasing Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The
relay contacts of this control panel may be used to trip any dialer that is UL listed for Central Station/Remote
Station services. The illustrations in this appendix provide examples of possible system configurations.
Note:
Applications which require the the NOTI-FIRE 911AC are not FM approved.
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
•
NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter
(DACT) connected to a
compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm
Communicator/Transmitter - Noti-Fire 911AC" on page 48 for installation instructions for this unit.
•
411UDAC Universal Digital Alarm Communicator
connected to a compatible listed Central
Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator
- 411UDAC" on page 49 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
•
4XTM Transmitter Module
for connection to a compatible listed Local Energy Municipal Box.
See "Local Energy Municipal Box" on page 50 for installation instructions for this unit.
NFPA 72 - Remote Station Fire Alarm System
•
Fire•Lite RS82-9 Remote Station Receiver
connected to a 4XTM Transmitter Module. See
"Remote Station Receiver - RS82-9" on page 51 for installation instructions for this unit.
•
NOTI-FIRE 911AC DACT
connected to a compatible listed Central Station DACR. See "Digital
Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 48 for installation instructions for
this unit
•
411UDAC Universal Digital Alarm Communicator
connected to a compatible listed Central
Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 49 for
installation instructions for this unit.
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...