Initiating Device Circuits
2. Installation
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
19
Four-Wire Smoke Detector Connections
A maximum of 200mA is available from the 24VDC Resettable Power circuit on TB1 (+24VR terminals).
Any power that is drawn from the 24VDC Nonresettable Power on TB2 (+24VNR terminal) must be
subtracted from available resettable power. See "Specifications" on page 12 and "Powering External
Devices" on page 22.
Note:
Refer to "Appendix B: Compatible Devices" on page 41 for suitable 4-wire smoke detectors.
Notes on Style D (Class A) and Style B (Class B) field wiring:
1.
The Power Supervision Relay coil leads must be connected to the last detector base 24V screw
terminals.
2.
Calculation of the maximum allowable resistance in the 24VDC resettable power wiring:
Where:
Rmax
= maximum resistance of the 24 VDC wires
Vom
= minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N
= total number of detectors on the 24 VDC supply circuit
Is
= detector current in standby
Na
= number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia
= detector current in alarm
Ir
= end-of-line relay current
Figure 8 Typical Connection for Four-Wire Smoke Detectors
Rmax =
(20.6 - Vom)
(N x Is) + (Na x Ia) + (Ir)
–
–
+
+
–
–
+
+
T B 1
T B 4
IN # 1
B + A + A – B –
I N
B + A +
M
S
44-4
w
ir
esd.cdr
24 VDC Four-wire
Smoke Detectors
4.7K, 1/2-Watt ELR
Power
Supervision
Relay
(A77-716B)
Style B
Initiating Device Circuit
Control Panel
Power Circuit
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...