2. Installation
Initiating Device Circuits
18
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Initiating Device Circuits
The control panel provides two Initiating Device Circuits (#1 and #2) and they may be configured as either
Style D (Class A) or Style B (Class B). Circuit #3 is designated as an Abort Switch Circuit and Circuit #4
is a Manual Release Circuit.
Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and
Waterflow alarm devices.
Note:
Refer to "Appendix B: Compatible Devices" on page 41 for compatible devices.
• Wire all alarm initiating devices sequentially for proper supervision.
• Observe polarity when connecting polarized devices.
• All circuits are supervised and power-limited.
• Leave dummy load resistor (provided) on all unused circuits.
Figure 7 Initiating Device Circuits
Style D (Class A)
Initiating Device
Circuit
Style B (Class B)
Initiating Device
Circuit
4.7K, 1/2-Watt resistor
PN 71252 (UL listed)
Style B (Class B)
Abort Switch
Circuit
Two-wire
Smoke
Detector
Manual
Pull Station
Heat
Detector
Style B (Class B)
Manual Release
Circuit
M
R
P
44-
idc.cdr
Note:
Silk screen printing on circuit board moved to bottom for clarity
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...