2. Installation
Optional Modules
24
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Installation - Lower Position
To install either the 4XTM, 4XZM or 4XLM module in the lower position follow these instructions:
Figure 14 Module Installation - Lower Position
Step
Action
1
Cut jumper ‘OPT2’ on main circuit board.
2
Remove the lower-right screw securing the main board to the lower rail.
Replace with a stand-off and tighten securely.
3
Insert one stand-off into the other hole located on the right-side edge of the
main board. Secure with nut and tighten securely.
4
Align the pins of J8 (and J7) connectors on the main board with the
holes on the underside of the J2 (and J1) connector on the optional
board. Carefully press down on the optional board until the pins are
through the connectors and it rests on the stand-offs.
5
Secure optional board to stand-offs with screws. Tighten securely.
6
Affix the terminal identification label (provided with the module) on the
back surface of the backbox, aligning it with the terminals on the module.
T B4
J4
J5
J 7
J 8
O PT1
O PT2
J 10
B –
IN # 2
B + A + A – B–
IN # 3
B + A + A – B–
IN # 4
B + A + A – B–
TB
1
J 2
M
S
4
4
-i
nstm
od2.
cdr
Install Stand-offs here
OPT2 -
Cut prior to
installation of module
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...