background image

LimWarLg.p65    01/10/2000

An automatic fire alarm system

–typically made up of smoke

detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers.  A study by the Federal Emer-
gency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires.  While fire alarm systems are de-
signed to provide early warning against fire, they do not guar-
antee warning or protection against fire.  A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot

reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors.  Smoke detectors
also may not sense a fire on another level or floor of a build-
ing.  A second-floor detector, for example, may not sense a
first-floor or basement fire.

Particles of combustion or "smoke"

 from a developing fire

may not reach the sensing chambers of smoke detectors be-
cause:

• Barriers such as closed or partially closed doors, walls, or

chimneys may inhibit particle or smoke flow.

• Smoke particles may become "cold," stratify, and not reach

the ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by air

outlets.

• Smoke detectors may be drawn into air returns before

reaching the detector.

The amount of "smoke" present may be insufficient to alarm
smoke detectors.  Smoke detectors are designed to alarm at
various levels of smoke density.  If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing
limitations.  Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke.  Detectors that have ion-
izing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires.  Because fires develop in differ-
ent ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detec-
tor may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).

Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a prede-
termined rate or reaches a predetermined level.  Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire pro-
tection specialist.  

Heat detectors are designed to protect

property, not life.

IMPORTANT! 

 Smoke detectors 

must be installed in the

same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power.  If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.

Audible warning devices

 such as bells may not alert people

if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion.  Please note that:

• Strobes can, under certain circumstances, cause seizures

in people with conditions such as epilepsy.

• Studies have shown that certain people, even when they

hear a fire alarm signal, do not respond or comprehend the
meaning of the signal.  It is the property owner's responsibil-
ity to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can

cause temporary or permanent hearing loss.

A fire alarm system

 will not operate without any electrical

power.  If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.

Equipment used in the system

 may not be technically com-

patible with the control.  It is essential to use only equipment
listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a

premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.

The most common cause

 of fire alarm malfunction is inade-

quate maintenance.  To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards.  At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed.  Environments with large amounts of
dust, dirt or high air velocity require more frequent mainte-
nance.  A maintenance agreement should be arranged
through the local manufacturer's representative.  Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized pro-
fessional fire alarm installers only.  Adequate written records
of all inspections should be kept.

While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!

Fire Alarm System Limitations

Содержание PDRP-1002 Series

Страница 1: ...PDRP 1002 Series Agent Release Control System Instruction Manual 3825 Ohio Avenue St Charles IL 60174 1 800 SENSOR2 Fax 630 377 6495 PN 51135 B0 ECN 00 543 Document 51135 I56 1358 01 04 06 2001 Rev B...

Страница 2: ...plosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined...

Страница 3: ...anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling...

Страница 4: ...Detectors NFPA 72 Installation Maintenance and Use of Notification Appliances for Fire Alarm Systems NFPA 72 Testing Procedures for Signaling Systems Underwriters Laboratories Documents UL 38 Manually...

Страница 5: ...Appliance and Releasing Circuits 12 Alarm and Trouble Relays 12 Resettable Power 12 Nonresettable Power 12 RMS Regulated Power 12 2 Installation Cabinet Mounting 13 Removal of Circuit Board 13 Mounti...

Страница 6: ...scharge Station Alarm Condition 37 Brownout Condition 37 Appendix A Secondary Power Calculations Standby Battery Requirements 39 Calculating the Battery Capacity 40 Appendix B Compatible Devices Two w...

Страница 7: ...d Power limited on all circuits except Municipal Box Output and Releasing Circuits Alarm and trouble resound Four Style B D Initiating Device Circuits Two Style Y Z Notification Appliance Circuits Two...

Страница 8: ...t 1 Style Y Releasing Circuit 2 Style Y Supervisory Input StyleB Front Panel Control Switches Switch 1 Tone Silence Switch 2 Alarm Silence Switch 3 Alarm Activate Switch 4 System Reset Suplemental Doc...

Страница 9: ...ET AC POW ER SYSTEM ALARM RELEASE SUPERVISORY SYSTEM TROUBLE CIRCUIT TROUBLE ALARM SILENCED POW ER TROUBLE ZONE 1 ABORT M ANUAL RELEASE MRP4424 board cdr Battery Fail LED Ground Fault LED SW1 DIP Swit...

Страница 10: ...e 14 6 ohms Maximum allowable wire resistance between panel and trip coil 3 ohms Municipal Box wiring can leave the building Specifications for Remote Station Service NFPA 72 Remote Station Fire Alarm...

Страница 11: ...formation Note The Remote Annunciator requires the use of an LED Interface Module as described below LED Interface Module 4XLM The LED Interface Module supports the RZA 4X Remote Annunciator Module An...

Страница 12: ...End of Line Resistor Notification Appliance and Releasing Circuits Power limited circuitry Maximum allowable voltage drop due to wiring 2 VDC Normal Operating Voltage 24 VDC Total current available to...

Страница 13: ...ckbox as required Determine the number of conductors required for the devices to be employed Pull required conductors into the box through the knockouts provided Note All wiring should be in accordanc...

Страница 14: ...llation of Circuit Board Reinstall the printed circuit board as follows Step Action 1 Position circuit board over stand offs on backbox rail and secure with four 4 phillips screws Tighten securely 2 C...

Страница 15: ...s the mounting location and connections for the Voltmeter Ammeter Figure 3 Mounting and Connecting the Meters Step Action 1 Cut the jumper wire labeled AMP 2 Secure the module to the backbox with the...

Страница 16: ...nection to the panel should be supplied to prevent voltage fluctuation and interruption of power Figure 4 AC Power Connections Battery DC Connections WARNING Battery contains sulfuric acid which can c...

Страница 17: ...m away from any nonpower limited circuit wiring Furthermore all power limited circuit wiring and nonpower limited circuit wiring must pass through separate knockouts and or conduits Figure 6 Power lim...

Страница 18: ...e Refer to Appendix B Compatible Devices on page 41 for compatible devices Wire all alarm initiating devices sequentially for proper supervision Observe polarity when connecting polarized devices All...

Страница 19: ...st be connected to the last detector base 24V screw terminals 2 Calculation of the maximum allowable resistance in the 24VDC resettable power wiring Where Rmax maximum resistance of the 24 VDC wires V...

Страница 20: ...easing Circuits see Releasing Circuits on page 21 cannot exceed 2 25 amps Note Refer to Appendix B Compatible Devices on page 41 for suitable devices For DIP switch configuration see Setting Mode of O...

Страница 21: ...Wiring Requirements on page 17 Each circuit is capable of 1 5 amps of current Total current drawn from both Releasing Circuits and both NACs see Notification Appliance Circuits on page 20 cannot excee...

Страница 22: ...cts Powering External Devices CAUTION Several different sources of power can be connected to this panel Disconnect all sources of power before servicing The panel and associated equipment may be damag...

Страница 23: ...structions Figure 13 Module Installation Upper Position Step Action 1 Cut jumper OPT1 on main circuit board 2 Insert the two stand offs into the holes located on the right side edge of the main board...

Страница 24: ...edge of the main board Secure with nut and tighten securely 4 Align the pins of J8 and J7 connectors on the main board with the holes on the underside of the J2 and J1 connector on the optional board...

Страница 25: ...nwillpreventunwantedactivationoftheMunicipalBoxduringtesting of the control panel The Disconnect LED will remain illuminated while the Municipal Box is disconnected The System Trouble LED will indicat...

Страница 26: ...cts are to be used as nonpower limited circuits write this on the Protected Premises Unit label located on the door of the control panel Figure 16 Wiring the Zone Relay Module The wiring of this modul...

Страница 27: ...wer off Maximum wire impedance is 50 ohm per wiring connection The wiring of this module must follow the requirements as specified under Power limited Wiring Requirements on page 17 Figure 18 Connecti...

Страница 28: ...on the other zone will shut this output off NAC 2 Activated by an alarm in either IDC 1 or IDC 2 Note The NAC will pulse at 60 ppm while timer is running or frozen by abort and will sound steady upon...

Страница 29: ...er will not operate when timer is set for No Delay Switch 5 OFF OFF ON ON Switch 6 OFF ON OFF ON Standard UL type delay timer IRI type delay timer NYC type delay timer Local Jurisdiction delay timer C...

Страница 30: ...1 is OFF Either Zone DIP 1 is ON Cross Zone DIP 2 is ON Supervisory Either Zone Cross Zone Relay 1 Activate when alarm is detected in Zone 1 or Zone 2 Activates when first alarm is detected in the sys...

Страница 31: ...amage and VOID WARRANTY Follow these steps to power up the FACP 1 Conduct Visual Inspection A careful visual inspection should be made before applying power to the system See Inspection on page 53 2 N...

Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...

Страница 33: ...flashes for any trouble condition including those associated with optional boards Circuit Trouble Yellow LED that flashes for trouble conditions on output circuits notification and releasing Alarm Sil...

Страница 34: ...ced LED will illuminate Alarm silence is a latching function and requires pressing SYSTEM RESET to clear Alarm Activate This switch may be used to activate Notification Appliance Circuits NACs It also...

Страница 35: ...operation is the default setting Canadian regulations require latching operation for programming instructions see Sprinkler Supervisory Tracking on page 36 Zone Disable If a zone has been disabled an...

Страница 36: ...s will be lost When power is restored Notification Appliance Circuit 1 will default to silenceable operation Sprinkler Supervisory Tracking The Initiating Device Circuit for sprinkler supervisory zone...

Страница 37: ...ized to release the suppressant agent Manual Discharge Station Alarm Condition Manual discharge does not use the predischarge timer If a manual station is used to initiate the alarm condition the foll...

Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...

Страница 39: ...ps Main Circuit Board 1 X 0 088 0 088 4XZM ZoneRelay Module X 0 008 4XTM Transmitter Module X 0 011 Reverse Polarity Alarm output X 0 005 Reverse Polarity Trouble output X 0 005 RZA 4X 4XLM Remote Ann...

Страница 40: ...table above Note Batteries must be lead acid type Standby Battery Current from Table 1 amps X Required Standby Time in Hours typically 241 602 or 903 hours hrs 1 NFPA 72 Central Station and Local and...

Страница 41: ...01 B401B B406B A 0 12 15 15 1 System Sensor 2451TH A Photo Thermal B401 B401B B406B A 0 12 15 15 1 System Sensor 2851DH A Photoelectric DH2851DC A 0 12 15 System Sensor 1451DH A Ionization DH400 A 0 1...

Страница 42: ...sor 2312 24TB Photoelectric 0 12 50 System Sensor B112LP Base See Note 39 System Sensor B114LP Base See Note 75 System Sensor B404B Base See Note See Note System Sensor 6424 Projected Beam 10 28 4 Sys...

Страница 43: ...245 210 System Sensor SS241575ADA Signaling Strobe 24VDC 120 93 System Sensor SS2415ADAS Signaling Strobe with Synch Circuit 24VDC 125 106 System Sensor SS241575ADAS Signaling Strobe with Synch Circu...

Страница 44: ...obe 24VDC 318 256 System Sensor MAEH2415ADAS Multi Alert Horn with Mechanical Tone Strobe 24VDC 198 152 System Sensor MAEH241575ADAS Multi Alert Horn with Mechanical Tone Strobe 24VDC 253 241 System S...

Страница 45: ...ers listed below Table 7 Door Holders 24 VDC Relays UL Listed Use the Relays listed below Table 8 24 VDC Relays Model Type Current mA FM 980 24 Floor Mount Single 68 FM 986 24 Wall Mount Surface Wirin...

Страница 46: ...Appendix B Compatible Devices 24 VDC Relays UL Listed 46 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...

Страница 47: ...pplications which require the the NOTI FIRE 911AC are not FM approved NFPA 72 Signaling Systems for Central Station Service Protected Premises Unit NOTI FIRE 911AC Digital Alarm Communicator Transmitt...

Страница 48: ...ntrol panel s backbox all connections must be in conduit less than 20 ft 609 6 cm in length in the same room For additional information refer to the Noti Fire 911AC Instruction manual Figure 24 DACT C...

Страница 49: ...e programmed accordingly Inthis example Zone 1 is wired to thecontrol panel s alarm relay Zone2 iswiredtothecontrolpanel stroublerelay andZone3iswiredtotheoptionalmodule ssupervisory relay AC power is...

Страница 50: ...nd faults and opens i e missing wire but not for direct short between two wires It is not a power limited circuit This application is not suitable for separate transmission of sprinkler supervisory or...

Страница 51: ...tation Receiver Intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings All connections are power limited and supervised with the exception...

Страница 52: ...Appendix C NFPA Standard Specific Requirements Remote Station Receiver RS82 9 52 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...

Страница 53: ...AC power and battery power 2 Disconnect the installed solenoid valve circuit leads an connect spare solenoid valves or connect an end of line device to serve as a dummy load 3 Reconnect AC power and...

Страница 54: ...ound fault trouble Earth yellow LED ON 1 Remove field wiring from main panel and optional module s if installed Install dummy ELR 4 7K 2 Remove both battery leads 3 If trouble clears connect one circu...

Страница 55: ...35 36 Central Station 47 48 49 charging current 15 circuit Remote Alarm 25 Remote Trouble 25 reverse polarity 10 circuit board 13 circuit breaker 16 CO2 releasing applications 33 conductors 13 conduit...

Страница 56: ...resistance 21 Maximum Battery Capacity 12 Maximum Charging Circuit 12 maximum resistance 19 Meter Module 11 15 microprocessor 33 minimum clearance 13 minimum voltage 21 module connectors 23 motherboa...

Страница 57: ...supervisory 50 Standard UL type delay timer 29 Standby Battery Current 39 stand off 14 23 24 Style B Class B 18 Style D Class A 18 Style Y Class B 20 21 Style Z Class A 20 sulfuric acid 31 supervised...

Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...

Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...

Страница 60: ...IL 60174 Please include a note describing the malfunction and suspected cause of failure This writing constitutes the only warranty made by System Sensor with respect to its products System Sensor do...

Отзывы: