PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
41
Appendix B: Compatible Devices
Two-wire Smoke Detectors, UL Listed
Use the two-wire detectors listed below.
Table 3 Two-wire Smoke Detectors
Detector
Model
Identifier
Type
Base
Model
Identifier
Standby
Current
(mA)
Detectors
per Zone
System Sensor 1400
A
Ionization
n/a
n/a
0.10
20
System Sensor 1451
A
Ionization
B401/B401B/
B406B
A
0.12
15/15/1
System Sensor 1851DH
A
Ionization
DH1851DC
A
0.12
15
System Sensor 2400
A
Photoelectric
n/a
n/a
0.12
15
System Sensor 2400AIT
A
Photo/
Isolated
Thermal/Horn
n/a
n/a
0.12
15
System Sensor 2400AT
A
Photo/
Thermal/Horn
n/a
n/a
0.12
15
System Sensor 2400TH
A
Photo/
Thermal
n/a
n/a
0.12
15
System Sensor 2451
A
Photoelectric
B401/B401B/
B406B
A
0.12
15/15/1
System Sensor 2451TH
A
Photo/
Thermal
B401/B401B/
B406B
A
0.12
15/15/1
System Sensor 2851DH
A
Photoelectric
DH2851DC
A
0.12
15
System Sensor 1451DH
A
Ionization
DH400
A
0.12
15
System Sensor 2451
A
Photoelectric
DH400
A
0.12
15
System Sensor 2300T
A
Photo/
Thermal
n/a
n/a
0.12
15
System Sensor 1800
A
Ionization
n/a
n/a
0.12
n/a
System Sensor 1851B
A
Ionization
B101B
A
0.12
n/a
System Sensor 1851B
A
Ionization
B107B
A
0.12
n/a
System Sensor 2800
A
Photoelectric
n/a
n/a
0.12
n/a
System Sensor 2800TH
A
Photo/
Thermal
n/a
n/a
0.12
n/a
System Sensor 2851B
A
Photoelectric
B101B
A
0.12
n/a
System Sensor 2851B
A
Photoelectric
B107B
A
0.12
n/a
System Sensor 2851BTH
A
Photo/
Thermal
B101B
A
0.12
n/a
System Sensor 2851BTH
A
Photo/
Thermal
B107B
A
0.12
n/a
System Sensor 1151
A
Ionization
B401/
B110LP/
B116LP
A
0.12
15/15/1
System Sensor 2151
A
Photoelectric
B401/
B110LP/
B116LP
A
0.12
15/15/1
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...