Appendix C: NFPA Standard-Specific Requirements
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
48
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Note:
This application is not FM approved
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises
Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less
than 20 ft. (609.6 cm) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
Figure 24 DACT Connections
G E N
A LM 2
T B3
T B4
JP 1
S U P V 1
S U P R 2
G E N
A LM 1
O P T 1
IN #1
B + A + A– B –
IN #2
B + A + A– B –
IN #3
B + A + A– B –
IN #4
B + A + A– B –
TB 1
LATC H
DIS A BL E
J 2
STD DA C T
+
–
TB 3
MS
44
-9
1
1
ac
.c
d
r
Place jumper over pins as shown when employing
a DACT. This directs the control panel to transmit
all trouble conditions except AC LOSS.
To Central
Station
PS 1270
12Volt
7AH Battery
To AC Power
See Below for Terminal
Connections
Control Panel
4XZM Zone
Relay Module
To Common
Terminal of Relay
Jumper
Содержание PDRP-1002 Series
Страница 32: ...2 Installation Power Up Procedure 32 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 38: ...3 System Operation System Events 38 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 Notes...
Страница 58: ...58 PDRP 1002 Instruction Manual PN 51135 B0 04 06 01...
Страница 59: ...PDRP 1002 Instruction Manual PN 51135 B0 04 06 01 59...