6.6.10 LC/HP version: unit installed at a higher level than the remote exchanger
There must be syphons on the vertical sections of the suction/delivery line "G" to facilitate oil return to the compressor. The
height "h" must be less than 4 metres.
The horizontal sections of the suction/delivery line "G" must not slope at all.
6.6.11 LC/HP version: unit installed at a lower level than the remote exchanger
There must be syphons on the vertical sections of the suction/delivery line "G" to facilitate oil return to the compressor. The
height "h" must be less than 4 metres.
The horizontal sections of the suction/delivery line "G" must not slope at all.