2.2.9 Condensation control at the source hydraulic circuit for HP units
For the source-side heat exchanger, the hydraulic circuit of the reversible heat pump units requires a pressure switch valve,
a by-pass solenoid valve and a second paddle flow switch.
For some models, these components are already installed in the unit whereas for others, they are assembled in kits and
supplied loose with the unit.
If the kit is supplied loose with the unit, it is mandatory to install it and this must be done by the installer.
The flow switch in the source hydraulic circuit should be installed on the heat exchanger outlet, with the same measures
used for the flow switch of the user circuit.
Fig. 3 Connection of pressure switch valve, solenoid valve and flow switch
02
Condenser
40
Pressure switch valve
YV
Solenoid valve
FL
Flow switch