Translation from original instructions
3.3 Handling
Before each unit handling operation, check that the lifting capacity of the machinery used is compatible with the weight of
the unit.
Handling must be carried out by adequately equipped qualified personnel.
In all lifting operations, make sure the unit is firmly secured in order to prevent accidental falls or overturning.
Lifting must be carried out by qualified and authorised personnel taking the necessary precautions; if carried
out incorrectly, lifting can cause serious damage and physical injury.
The handling operations must be carried out slowly and sudden manoeuvres and knocks must be avoided.
During unloading and positioning of the unit, great care must be taken to prevent sudden or violent manoeuvres, and the
components of the unit must not be used as lifting points.
All work on the unit, including unpacking and connections, must be carried out with the unit resting on the ground.
Refer, in any case, to the lifting instructions provided with the unit.
The units are dispatched screwed onto pallets having anti-overturning boards. To unload them from the vehicle, use a forklift
truck.
Insert the forks under the unit on the side where the anti-overturning boards are fixed, with the forks as far apart as possible,
until they protrude from the back of the base, and keep the centre of gravity of the unit centred between the forks.
Fig. 4 Lifting with forklift truck
If anti-vibration mounts are installed under the base of the unit, this must be done with the unit raised by no more than 200
mm from the ground and without putting any parts of the body under it.
Before sliding out the pallet, remove the screws fixing it to the unit.
3.4 Storage
The units are built to be installed in indoor environments.
Storage outdoors is not allowed. Upon receipt they must be put in locations protected from weather agents.
Since the remote condensing unit, if present, is designed to be installed outdoors, it can withstand outdoor atmospheric
conditions.
For the condensing unit, must be pay attention to the place where it is placed, which must be on the flat, in order to avoid
deformation of the structure with consequent possible breakage.