6.6.6 LE/HP version: unit installed at a lower level than the remote exchanger
Fit a syphon on the highest suction/delivery line "G" of the evaporator in order to prevent liquid refrigerant from going
towards the compressor when the unit is not running.
There must be syphons on the vertical sections of the suction/delivery line "G" to facilitate oil return to the compressor. The
height "h" must be less than 4 metres.
The horizontal sections of the suction/delivery line "G" must not slope at all.