2.2.4 Installing the flow switch
The units are shipped from the factory without the flow switch installed.
The flow switch is supplied with the unit and must be connected by the installer.
The flow switch is complete with cable for the electrical connection and the paddle that detects water flow is already fitted.
The flow switch must be inserted on the water pipe at the outlet of the unit in a straight and horizontal section of the pipe
well away from filters, valves etc. at a distance of at least 5 times the pipe diameter both upstream and downstream.
The arrow on the switch must be aligned with the water flow.
The flow switch is factory calibrated for installation on a horizontal pipe.
The push rod must be in the vertical position.
The electrical connection of the flow switch should be made in the terminal board of the electrical control panel using the
prepared terminals as shown in the wiring diagram.
Lock the cable in place with cable ties in the section between the flow switch and the inlet to the electrical control panel.
2.2.5 Hydraulic components for reversible heat pump units
For the source-side heat exchanger, the hydraulic circuit of the reversible heat pump units requires a pressure switch valve,
a by-pass solenoid valve and a second paddle flow switch.
For some models, these components are already installed in the unit whereas for others, they are assembled in kits and
supplied loose with the unit.
If the kit is supplied loose with the unit, it is mandatory to install it and this must be done by the installer.
The flow switch in the source hydraulic circuit should be installed on the heat exchanger outlet, with the same measures
used for the flow switch of the user circuit.