IEC16000160-1-en.vsdx
Priority
AND
OR
High (Master)
inProgress
unsuccessful
WFMASTER
Master:
Slave:
Priority
Low (Slave)
AND
AND
start
WAIT
t
tWaitForMaster
AND
AND
S
R
OR
inhibit
commandCloseCB
reclaimTimeStarted
inhibitWaitForMaster
slaveDeadTime
wait
IEC16000160 V1 EN-US
Figure 115:
Master-Slave
If reclosing of the first circuit breaker is unsuccessful, the
UNSUCCL
output
connected to the
INHIBIT
input of the slave unit interrupts the reclosing sequence
of the latter. The signals can be cross-connected to allow simple changing of the
priority by just setting the High and the Low priorities without changing the
configuration. The
CBCLOSED
inputs from each circuit breaker are important in
multi-breaker arrangements to ensure that the circuit breaker was closed at the
beginning of the sequence. If the High priority breaker was not closed its auto
reclosing sequence will not start and the low priority breaker will just continue its
auto reclosing sequence in accordance with its normal settings.
9.2.6.5
Time sequence diagrams
M12458-10 v5
Some examples of the timing of internal and external signals at typical transient
and permanent faults are shown below in Figure
.
Section 9
1MRK 505 384-UEN A
Control
262
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...