
9.4.9
Proxy for signals from switching device via GOOSE
XLNPROXY
9.4.9.1
Functionality
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
The proxy for signals from switching device via GOOSE (XLNPROXY) gives an
internal representation of the position status and control response for a switch
modelled in a breaker IED. This representation is identical to that of an SXCBR or
SXSWI function.
9.4.9.2
Function block
GUID-408513CD-A87E-45E8-8E44-24E153947F02 v1
XLNPROXY
BEH*
BEH_VALID*
LOC*
LOC_VALID*
BLKOPN*
BLKOPN_V*
BLKCLS*
BLKCLS_V*
POSVAL*
POSVAL_V*
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN
XPOS
SELECTED
OP_BLKD
CL_BLKD
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
EEHEALTH
OPCAP
IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US
Figure 145:
XLNPROXY function block
9.4.9.3
Signals
PID-6712-INPUTSIGNALS v3
Table 175:
XLNPROXY Input signals
Name
Type
Default
Description
BEH
INTEGER
-1
Behaviour
BEH_VLD
BOOLEAN
0
Valid data on BEH input
LOC
BOOLEAN
0
Local control behaviour
LOC_VLD
BOOLEAN
0
Valid data on LOC input
BLKOPN
BOOLEAN
0
Block opening
BLKOPN_VLD
BOOLEAN
0
Valid data on BLKOPN input
BLKCLS
BOOLEAN
0
Block closing
Table continues on next page
1MRK 505 384-UEN A
Section 9
Control
Breaker protection REQ650 2.2 IEC
303
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...